Warning and Safety instructions
8
In order to ensure safe operation and to prevent gases given off by
the heating appliance from being drawn back into the room when
the cooker hood and the heater are both operated simultaneously,
an underpressure in the room of 0.04mbar (4Pa) is the maximum
permissible.
Sufficient ventilation can be maintained by air inlets which cannot
be blocked, e.g. in windows, doors and outside wall vents. The
cross-section of the inlet openings must enable sufficient
ventilation. A ventilation brick alone is not generally sufficient to
ensure safe ventilation.
The overall ventilation condition of the dwelling must be taken into
account. If in any doubt, ask a competent building regulations
inspector or qualified gas fitter (if appropriate).
If the cooker hood is being operated in recirculation mode, whereby
the air is redirected into the room in which it is installed, the above
restrictions do not apply.
Correct use
Open flames are a fire hazard.
The use of an open flame under the cooker hood is not permitted. To
avoid the danger of fire, do not flambé or grill over an open flame.
When switched on, the cooker hood could draw flames into the filter.
Fat deposits could ignite, presenting a fire hazard.
The cooker hood can become damaged when exposed to
excessive heat.
- When using the cooker hood over a gas hob, ensure that any
burners in use are always covered by a pan. Switch the cooking
zone off when a pan is removed, even for a short time.
- Select a pan which is suitable for the size of the burner.
- Regulate the flame so that it does not burn up the sides of the pan.
- Avoid overheating the pan (e.g. when cooking with a wok).
Always switch the cooker hood on when a cooking zone is in use,
otherwise condensation may collect in the hood, which could cause
corrosion.