(N) Operation via communication and its settings Parameters
5 - 530
Ethernet communication network number (Pr. 1424),
Ethernet communication station number (Pr. 1425)
When the MELSOFT / FA product connection, SLMP, or iQSS is selected for Ethernet communication,
enter the Ethernet communication network number in Pr. 1424 and the Ethernet communication sta-
tion number in Pr. 1425.
5.12.9 MELSOFT / FA product connection
FR Configurator2, GOT, or a relay station (programmable controller) can be connected via Ethernet.
Initial setting
â—Ź Set any value from "5000 to 5002, 5006 to 5008" in any of Pr. 1427 to Pr. 1429 (Ethernet function
selection 1 to 3) to select the MELSOFT / FA product connection for the application. (For how to
set the application value, refer to the Instruction Manual of the device connected via Ethernet.)
(Refer to page 5-524.)
â—Ź Enter the Ethernet communication network number in Pr. 1424 and the Ethernet communication
station number in Pr. 1425. (Refer to page 5-530.)
● Enable the PLC function (Pr. 414 "PLC function operation selection" ≠"0 (initial value)") to use FR
Configurator2 (Developer). (For the details of Pr. 414, refer to page 5-439.)
System configuration
I003115E
Fig. 5-256: MELSOFT / FA product connection system configuration
Direct connection with FR Configurator2
Direct connection with GOT
Connection using a relay station
(programmable controller)
Ethernet cable
Ethernet cable
Ethernet cable
Inverter
Inverter
Inverter
Personal computer
(FR Configurator2)
GOT
Relay station
(programmable controller)