EasyManua.ls Logo

Mitsubishi FDT100VNXWVH - Louver Motor Failure

Mitsubishi FDT100VNXWVH
202 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
-
87
-
'20 • PAC-SM-351
Error code
Remote control:
LED Green Red
Indoor
Outdoor
Content
None
Louver motor failure
Keeps ashing
Stays OFF
Keeps ashing
Stays OFF
1. Applicable model
5. Troubleshooting
FDT, FDTC, FDE series
Diagnosis Countermeasure
NO
YES
Is LM wiring
broken?
Is LM locked?
▲ Check at the indoor unit side.
LM: louver motor
Is the louver
operable with the remote
control?
YES
NO
Does the louver
operate at the power
on?
YES
NO
YES
NO
Operate after
waiting for more
than 1 minute.
Repair wiring.
Defective indoor unit
control PCB
Replace.
Replace LM.
Normal
Adjust LM lever and then
check again.
2. Error detection method
3.
Condition of error displayed
4. Presumable cause
Defective LM
LM wire breakage
Faulty indoor unit control
PCB
Note:

Related product manuals