'22 • PAC-SM-412
-
12
-
(6) Hot keep
Hot keep control is performed at the start of the defrost operation.
(a) Contents of operation
(i)Whentheindoorheatexchangertemperature(detectedwithThi-R1orR2)dropstolessthan35°C,thespeedofindoor
fanfollowsfansettingatthetimeofthermostatOFF.
(ii)Duringthehotkeep,thelouveriskeptatthehorizontalposition.
(7) Auto swing control (FDT, FDE only)
Note Even if [Auto Swing] is selected, the louver position with anti draft function is fixed to position 1.
(a) RC-EXZ3A
(i)Louvercontrol
1)Tooperatetheswinglouverwhentheair-conditionerisoperating,pressthe“Direction”buttonontheTOPscreen
of remote control. The wind direction select screen will be displayed.
2)Toswingthelouver,touchthe“Autoswing”button.Theloverwillmoveupanddown.Toxtheswinglouverata
position,touchoneof[1]-[4]buttons.Theswingloverwillstopattheselectedposition.
3)Louveroperationatthepoweronwithaunithavingthelouver4-positioncontrolfunction
Thelouverswingsonetimeautomatically(withoutoperatingtheremotecontrol)atthepoweron.
Thisallowsthemicrocomputerrecognizingandinputtingthelouvermotor(LM)position.
(ii)Automaticlouverlevelsettingduringheating
At the hot start andthe heatingthermostat OFF, regardless whether the auto swing switch is operated ornot (auto
swingorlouver stop), the louvertakes thelevelposition (in order to preventblowing ofcoolwind).The louver
positiondisplayLCDcontinuestoshowthedisplaywhichhasbeenshownbeforeenteringthiscontrol.
(iii)Louverfreestopcontrol
Ifyoutouchthe“Menu”→“Servicesetting”→“R/Csettings”→“Servicepassword”buttonsoneafteranotheron
theTOPscreenofremotecontrol,the“Flapcontrol”screenisdisplayed.Ifthefreestopisselectedonthisscreen,the
louvermotorstopsuponreceiptofthestopsignalfromtheremotecontrol.Iftheautoswingsignalisreceivedfrom
theremotecontrol,theautoswingwillstartfromthepositionbeforethestop.
(b) RC-E5
(i)Louvercontrol
1)Pressthe“LOUVER”buttontooperatetheswinglouverwhentheair-conditionerisoperating.
“SWING
”isdisplayedfor3secondsandthentheswinglouvermovesupanddowncontinuously.
2)Toxtheswinglouverataposition,pressonetimethe“LOUVER”buttonwhiletheswinglouverismovingso
that four stop positions are displayed one after another per second.
Whenadesiredstoppositionisdisplayed,pressthe“LOUVER”buttonagain.Thedisplaystops,changestoshow
the “STOP 1
”for5secondsandthentheswinglouverstops.
3)Louveroperationatthepoweronwithaunithavingthelouver4-positioncontrolfunction
Thelouverswingsonetimeautomatically(withoutoperatingtheremotecontrol)atthepoweron.
Thisallowsinputtingthelouvermotor(LM)position,whichisnecessaryforthemicrocomputerto recognizethe
louverposition.
Note(1)Ifyoupressthe“LOUVER”button,theswingmotionisdisplayedonthelouverpositionLCDfor10seconds.Thedisplaychangestothe
“SWING
” display 3 seconds later.
(ii)Automaticlouverlevelsettingduringheating
Atthehotstart with the heating thermostat OFF, regardless whether the auto swing switch is operated or not (auto
swingorlouver stop), the louver takesthe levelposition(Inorder to prevent the coldstart).The louver position
displayLCDcontinuestoshowthedisplaywhichhasbeenshownbeforeenteringthiscontrol.
(iii)Louver-freestopcontrol
Whenthelouver-freestophasbeenselectedwiththeindoorfunctionofwiredremotecontrol“
POSITION”, the
louvermotorstopswhenitreceivesthestopsignalfromtheremotecontrol.Iftheautoswingsignalisreceivedfrom
theremotecontrol,theautoswingwillstartfromthepositionwhereitwasbeforethestop.
Note (1) When the indoor function of wired remote control “ POSITION” has been switched, switch also the remote control function “
POSITION” in the same way.