'22 • PAC-SM-412
-
20
-
Individualoperation(Factorydefault) Allunitsoperation(Localsetting)
CnT-6 or
CnTA
ON OFF ON OFF
Only the unit
directly connected
to the remote control
can be operated.
Only the unit
directly connected
to the remote
control can be
stopped opeartion.
Allunitsinone
remote control
system can be
operated.
Allunitsinone
remote control
system can be
stopped operation.
Unit
only Unit
only Units
①-Ⓕ
Units
①-Ⓕ
Whenmorethanoneindoorunit(Max.16indoorunits)areconnectedinonewiredremotecontrolsystem:
(1) Withthefactorydefault,externalinputtoCnT-6orCnTAiseectiveforonlytheunit
.
(2) Whensetting“Forallunit”(Localsetting),allunitsinoneremotecontrolsystemcanbecontrolledbyexternal
inputtoCnT-6orCnTAontheindoorunit
.
(3) ExternalinputtoCnT-6orCnTAontheotherindoorunitthantheunit
isnoteective.
(21) Operation permission/prohibition
(In case of adopting card key switches or commercially available timers)
When the indoorfunction setting of wired remote control for “Operationpermission/prohibition” is changed from
“Invalid(Factorydefault)”to“Valid”,followingcontrolbecomeseective.
CnT
CnTA
XR5
XR1
1
2
3
4
5
6
XR3
XR4
XR2
Option
XR5
Note (1)
 
CnTAfunctioncanbe
changedbyRC-EXZ3A.
XR6
1
2
Normal operation
(Factorydefault)
Operationpermission/prohibitionmode
“Valid”(Localsetting)
CnT-6 or
CnTA
ON OFF ON OFF
Operation Stop
Operation
permission*1
Operation prohibition
(Unit stops)
*1
Only the LEVEL INPUT is acceptable for external input
,howeverwhentheindoorfunctionsettingof
Levelinput(Factorydefault)” or Pulse input is selected by the function for External input of the wired
remotecontrol,operationstatuswillbechangedasfollows.
Incaseof“Levelinput”setting Incaseof“Pulseinput”setting
Unit operation from the wired
remote control becomes
available
1
Unit starts operation
2
1)Incasethat“Operationpermission/prohibitionmode”settingis“Valid”and“Externalinput”settingis“Level
input(Factorydefault)”;
WhencardkeyswitchisON(CnT-6orCnTAON:Operationpermission),start/stopoperationoftheunit
fromthewiredremotecontrolbecomesavailable.
②
WhencardkeyswitchisOFF(CnT-6orCnTAOFF:Operationprohibition),theunitstopsoperationin
conjunctionwithOFFsignal,andstart/stopoperationoftheunitfromthewiredremotecontrolbecomes
unavailable.
2)Incasethat“Operationpermission/prohibitionmode”settingis“Valid”and“Externalinput”settingis
“Pulseinput(Localsetting)”;
WhencardkeyswitchisON(Operationpermission),theunitstartsoperationinconjunctionwithONsignal,
andalsostart/stopoperationoftheunitfromthewiredremotecontrolbecomesavailable.
WhencardkeyswitchisOFF(Operationprohibition),theunitstopsoperationinconjunctionwithOFFsignal,
andstart/stopoperationoftheunitfromthewiredremotecontrolbecomesunavailable.
3)Thisfunctionisinvalidonlyat“Centermode”settingdonebycentralcontrol.