'22 • PAC-SM-412
-
22
-
(22) Temporary stop input
Incaseoftemporarystop,operationlampofremotecontrollights,butindoor/outdoorunitstoptheoperation.
(a) In case of “level input” setting (Factory default)
InputsignaltoCnT-6orCnTAisOFF→ON:Temporarystop
InputsignaltoCnT-6orCnTAisOFF→ON:Normaloperation
(b) In case of “pulse input” setting (Local setting)
ItiseectiveonlywhentheinputsignalischangedOFF→ON,and“temporarystop/normaloperation”isinverted.
CnT-6 or CnTA input
OFF
ON
OFF
ONON
Actual operation
ON
ON
Temporary stop
Temporary stop
OFF
Remote control
ON
OFF
Normal operation/
Te mporary stop zone
Normal
Temporary stop
Normal
Temporary stop
OFF
(23) Selection of cooling/heating external input function
(a)When“Externalinput1setting:Cooling/heating”issetbytheindoorunitfunctionfromremotecontrol,thecoolingor
heatingisselectedwithCnT-6orCnTA.
(b)Whentheexternalinput1methodselection:Levelinputissetbytheindoorunitfunction:
CnT-6orCnTA:OPEN→Coolingoperationmode
CnT-6orCnTA:CLOSE→Heatingoperationmode
(c)Whentheexternalinput1methodselection:Pulseinputissetbytheindoorunitfunction:
IftheexternalinputischangedOPEN→CLOSE,operationmodesareinverted(Cooling→HeatingorHeating→
Cooling).
(d)If thecooling/heatingselectionsignal is given bytheexternalinput, the operation modeistransmittedto the remote
control.
Selectionofcooling/heatingexternalinputfunction
External input selection
External input selection
Cooling/heating selection
External input method
Level
External terminal input
(CnT or CnTA)
Cooling/heating
Cooling/heating
(Competitive)
External terminal input
(CnT or CnTA)
Cooling/heating
Cooling/heating
(Competitive)
⑥Pulse
Operation
OFF
Cooling zone
Heating zone Cooling zone
Cooling zoneHeating zone Heating zone
OFF
ON
OFFOFF
ON ON
ON
Cooling
Heating Heating
Cooling
Cooling
Cooling
Auto
Auto
Cooling
Auto, cooling, dry mode command
from remote control
Heating, auto, heating mode
command from remote control
Set “Cooling/
Heating” “Pulse”
Auto, cooling, dry mode
command by remote control
Auto, heating mode
command by remote control
After setting “Cooling/heating selection”, the cooling/heating is
selected by the current operation mode.
During heating : Set at the heating zone (cooling prohibition zone).
During cooling, dry, auto and fan mode: Set
at cooling zone (heating prohibition zone).
Heating
Heating
Heating
Cooling
Heating
Cooling
Cooling
Note(1) RegardingthepriorityorderforcombinationsofCnTandCnTA,refertopage18.
CnT-6 or CnTA input
OFF
ON
OFF
ON
Actual operation
ON
ON
Temporary stop
Temporary stop
OFF
Remote control
ON
OFF

Table of Contents