(d) Detail of opepation
(i)Changeoperationmodetocooling.
(ii)Thecompressorspeedisxedat40rps.
(iii)TheopeningoftheEEVisxedat470pulses.
1)Whenoutdoorairtemperature(TH2)anddischargepipetemperature(TH3)areinthecontrolrange(A)
①
Refrigerantejectioncontrol(2minutes)
②
Compressor stop (1 minute)
③
Normalheatingoperation
2)Whenoutdoorairtemperature(TH2)anddischargepipetemperature(TH3)areinthecontrolrange(B)
①
Refrigerantejectioncontrol(2minutes)
②
Compressor stop (1 minute)
③
Refrigerantejectioncontrol(2minutes)
④
Compressor stop (1 minute)
⑤
Refrigerantejectioncontrol(2minutes)
⑥
Afterstoppingthecompressorfor3minutes,startheatingoperation.
(-15,0)
TH3[°C]
Control range(A)