'22 • PAC-SM-412
-
37
-
(ii) Outdoor unit
Remote control
Indoor unit control PCB
Location of trouble Description of trouble Repair method
Reference
page
Error code Red LED Red LED
Green
LED
Keeps
flashing
StaysOFF
Keeps
flashing
Installation, operation status
•Higheroutdoorheatexchangertemperature
Repair
81
Outdoorheatexchanger
temperature sensor
•Defectiveoutdoorheatexchangertemperaturesensor
Replacement, repair
of temperature
sensor
Outdoor unit PCB
*•DefectiveoutdoorunitPCB(Defectivetemperaturesensorinputcircuit)?
Replacement of
PCB
StaysOFF
Keeps
flashing
Installation, operation status
•Higherdischargetemperature
Repair
82
Dischargepipetemperature
sensor
•Defectivedischargepipetemperaturesensor
Replacement, repair
of temperature
sensor
Outdoor unit PCB
*•DefectiveoutdoorunitPCB(Defectivetemperaturesensorinputcircuit)?
Replacement of
PCB
StaysOFF
Keeps
flashing
Outdoorheatexchanger
temperature sensor
•Defectiveoutdoorheatexchangertemperaturesensor,brokenwireorpoor
connector connection
Replacement, repair
of temperature
sensor
83
Outdoor unit PCB
*•DefectiveoutdoorunitPCB(Defectivetemperaturesensorinputcircuit)?
Replacement of
PCB
StaysOFF
Keeps
flashing
Outdoor air temperature sensor
•Defectiveoutdoorairtemperaturesensor,brokenwireorpoorconnector
connection
Replacement, repair
of temperature
sensor
84
Outdoor unit PCB
*•DefectiveoutdoorunitPCB(Defectivetemperaturesensorinputcircuit)?
Replacement of
PCB
StaysOFF
Keeps
flashing
Dischargepipetemperature
sensor
•Defectivedischargepipetemperaturesensor,brokenwireorpoorconnector
connection
Replacement, repair
of temperature
sensor
85
Outdoor unit PCB
*•DefectiveoutdoorunitPCB(Defectivetemperaturesensorinputcircuit)?
Replacement of
PCB
StaysOFF
Keeps
flashing
Installation, operation status
•Servicevalve(gasside)closingoperation
Replacement
86
StaysOFF
Keeps
flashing
Outdoor unit PCB, compressor
•Currentcut(Anomalouscompressorover-current)
Replacement of
PCB
87・88
Installation, operation status
•Servicevalveclosingoperation
Repair
StaysOFF
Keeps
flashing
Outdoor unit PCB
•Overvoltage
Repair
PCB replacement
89
•Defectiveactivefilter
StaysOFF
Keeps
flashing
Fanmotor
•Defectivefanmotor
Replacement
90
Outdoor unit PCB
•DefectiveoutdoorunitPCB
StaysOFF
Keeps
flashing
Power transistor error
(Outdoor unit PCB)
• Power transistor error
Replacement of
PCB
91
StaysOFF
Keeps
flashing
Operation status
•Shortageinrefrigerantquantity
Repair
92
Installation status
•Servicevalveclosingoperation
Servicevalve
openingcheck
StaysOFF
Keeps
flashing
•Overloadoperation
•Overcharge
•Compressorlocking
• Current safe stop
Replacement
93
StaysOFF
Keeps
flashing
Compressor, outdoor unit PCB
•Anomalouscompressorstartup
•Voltagedrop
Replacement
94
StaysOFF
Keeps
flashing
Compressor
•Anomalouscompressorrotorlock
Replacement
95
Note(1) *markinthedescriptionoftroublemeansthat,inordinarydiagnosis,itcannotidentifythecausedenitely,and,ifthetroubleisrepairedbyreplacingthe
part,itisjudgedconsequentlythatthereplacedpartwasdefective.