37
-
(ii) Outdoor unit
Remote control
Indoor unit control PCB
Location of trouble Description of trouble Repair method
Reference
page
Error code Red LED Red LED
Green
LED
Keeps
flashing
StaysOFF
Keeps
flashing
Installation, operation status
•Higheroutdoorheatexchangertemperature
Repair
81
Outdoorheatexchanger
temperature sensor
•Defectiveoutdoorheatexchangertemperaturesensor
Replacement, repair
of temperature
sensor
Outdoor unit PCB
*•DefectiveoutdoorunitPCB(Defectivetemperaturesensorinputcircuit)?
Replacement of
PCB
StaysOFF
Keeps
flashing
Installation, operation status
•Higherdischargetemperature
Repair
82
Dischargepipetemperature
sensor
•Defectivedischargepipetemperaturesensor
Replacement, repair
of temperature
sensor
Outdoor unit PCB
*•DefectiveoutdoorunitPCB(Defectivetemperaturesensorinputcircuit)?
Replacement of
PCB
StaysOFF
Keeps
flashing
Outdoorheatexchanger
temperature sensor
•Defectiveoutdoorheatexchangertemperaturesensor,brokenwireorpoor
connector connection
Replacement, repair
of temperature
sensor
83
Outdoor unit PCB
*•DefectiveoutdoorunitPCB(Defectivetemperaturesensorinputcircuit)?
Replacement of
PCB
StaysOFF
Keeps
flashing
Outdoor air temperature sensor
•Defectiveoutdoorairtemperaturesensor,brokenwireorpoorconnector
connection
Replacement, repair
of temperature
sensor
84
Outdoor unit PCB
*•DefectiveoutdoorunitPCB(Defectivetemperaturesensorinputcircuit)?
Replacement of
PCB
StaysOFF
Keeps
flashing
Dischargepipetemperature
sensor
•Defectivedischargepipetemperaturesensor,brokenwireorpoorconnector
connection
Replacement, repair
of temperature
sensor
85
Outdoor unit PCB
*•DefectiveoutdoorunitPCB(Defectivetemperaturesensorinputcircuit)?
Replacement of
PCB
StaysOFF
Keeps
flashing
Installation, operation status
•Servicevalve(gasside)closingoperation
Replacement
86
StaysOFF
Keeps
flashing
Outdoor unit PCB, compressor
•Currentcut(Anomalouscompressorover-current)
Replacement of
PCB
8788
Installation, operation status
•Servicevalveclosingoperation
Repair
StaysOFF
Keeps
flashing
Outdoor unit PCB
•Overvoltage
Repair
PCB replacement
89
•Defectiveactivefilter
StaysOFF
Keeps
flashing
Fanmotor
•Defectivefanmotor
Replacement
90
Outdoor unit PCB
•DefectiveoutdoorunitPCB
StaysOFF
Keeps
flashing
Power transistor error
(Outdoor unit PCB)
• Power transistor error
Replacement of
PCB
91
StaysOFF
Keeps
flashing
Operation status
•Shortageinrefrigerantquantity
Repair
92
Installation status
•Servicevalveclosingoperation
Servicevalve
openingcheck
StaysOFF
Keeps
flashing
•Overloadoperation
•Overcharge
•Compressorlocking
• Current safe stop
Replacement
93
StaysOFF
Keeps
flashing
Compressor, outdoor unit PCB
•Anomalouscompressorstartup
•Voltagedrop
Replacement
94
StaysOFF
Keeps
flashing
Compressor
•Anomalouscompressorrotorlock
Replacement
95
Note(1) *markinthedescriptionoftroublemeansthat,inordinarydiagnosis,itcannotidentifythecausedenitely,and,ifthetroubleisrepairedbyreplacingthe
part,itisjudgedconsequentlythatthereplacedpartwasdefective.