'22 • PAC-SM-412
-
41
-
Replace and set up the PCB according to this instruction.
i) Set to an appropriate address and function using switch on PCB.
 
Select the same setting with the removed PCB.
ii) Set to an appropriate capacity using the model selector switch(SW6).
Select the same capacity with the PCB removed from the unit.
iii) Replace the PCB
Exchange PCB after detaching all connectors connected with the PCB.
Fix the PCB so as not to pitch the wiring.
Connect connectors to the PCB. Match the wiring connector to the connector color on the PCB and connect it.
iv) Control PCB
Parts mounting are different by the kind of PCB.
〇:ON -:OFF
Item
Switch
Address
SW2
SW5-1
Content of control
Plural indoor units control by 1 remote control
Test run SW7-1
Normal
Operation check/drain pump motor test run
SW6
ON
1 2 3 4
SW6 -1 -2 -3 -4
125VH
Part number
SW5
Master/Slave
setting
SW2(Blue)
Address setting
CNI(Blue
Float SW
CNG(Blue
Motion sensor
CNV2(Black
Motion sensor
CNH(Black)
Thermistor
(
Return air
)
CNB(White)
Remote
control
CNTA(Blue)
External
input
CNW2(White)
Power 1 PCB
CNR(White)
Drain motor
CNTBlue
External switch
CNJ(White)
Louver motor
CNZ(White)
LED2
(Green)
LED3
(Red
HA
CNN(Yellow)
Thermistor
(Heat exchanger)
SW6
Capacity setting
SW7
Function setting
SW8
Function setting
CNE(White)
RAM checker
1) Control PCB
PSB012D990B
D
(b) Models FDU, FDUA, FDE series