EasyManua.ls Logo

Mitsubishi FDT71VH - E10 Excessive Number of Connected Indoor Units (more than 17 Units) by Controlling with One Remote Control

Mitsubishi FDT71VH
202 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
-
102
-
'20 • PAC-SM-351
Error code
Remote control:
LED Green Red
Indoor
Outdoor
Content
E10
Excessive number of connected
indoor units (more than 17 units)
by controlling with one remote control
Keeps ashing
Stays OFF
Keeps ashing
Stays OFF
1. Applicable model
5. Troubleshooting
Diagnosis Countermeasure
Are more than 17
indoor units connected to one
remote control?
NO
YES
Defective remote control
Replace.
Reduce to 16 or less units.
2. Error detection method
When it detects more than 17 of
indoor units connected to one
remote contorl
3 .
Condition of error displayed
Same as above
4. Presumable cause
Excessive number of indoor
units connected
Defective remote control
Note: