EasyManua.ls Logo

Mitsubishi FDT71VH - Page 161

Mitsubishi FDT71VH
202 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
-
160
-
'20 • PAC-SM-351
Error code
Remote control:
Content
1-time flashKeeps flashing
1-time flash
1-time flashON
Indoor display
RUN light TIMER light
Green LED
Yellow LED
Red LED
Outdoor unit
control PCB
Outdoor unit
inverter PCB
E42
Current cut (1/2)
1. Applicable model
5. Troubleshooting
All models
Diagnosis Countermeasure
Is the
Power source
voltage OK?
YES
Are the
service valves
opened?
NO
YES
Is the
high pressure
during operation
OK?
YES
Is the
checked result of
insulation resistance and
resistance between terminals (1) of
compressor motor
OK?
YES
(1) 1.044 or more at 20°C (Models FDC100-140VNX-W)
1.044 or more at 20°C (Models FDC100-140VSX-W)
NO
NO
NO
To next page.
Check power source.
Open the service valves.
Check refrigerant amount
and refrigerant circuit
* In case of transitional
increase of high pressure
and/or test run, several
times restarting may
recover it, because liquid
refrigerant (migrated)
in the compressor is
discharged from the
compressor.
Replace compressor.
2. Error detection method
In order to prevent from
overcurrent of inverter,
if the current exceeds the
specications, it makes the
compressor stopping.
3 .
Condition of error displayed
If the output current of inveter
exceeds the specications,
it makes the compressor
stopping.
After 3-minute delay, the
compressor restarts, but if this
amonaly occurs 4 times within
30 minutes after the intial
detection.
4. Presumable cause
The service valves closed
Faulty power source
Insufficient refrigerant amount
Faulty compressor
Faulty power transistor
module
Note:

Related product manuals