38
-
'20 • PAC-SM-351
(ii) Contents of operation
1) Air capacity control
Model
Item
SRK50, 60ZSX-W
Twin
type
ULo
Upper limit of compressor's speed RangeA: 50 rps, RangeB: 50 rps, RangeC: 24 rps
Indoor fan 4th speed
Lo
Upper limit of compressor's speed RangeA: 50 rps, RangeB: 50 rps, RangeC: 24 rps
Indoor fan Adaptable to compressor speed
Auto, Me
Upper limit of compressor's speed RangeA: 50 rps, RangeB: 50 rps, RangeC: 30 rps
Indoor fan Adaptable to compressor speed
Hi
Upper limit of compressor's speed
RangeA: 70 rps (SRK60: 80 rps), RangeB: 50 rps,
RangeC: 30 rps
Indoor fan Adaptable to compressor speed
Triple
type
ULo
Upper limit of compressor's speed RangeA: 50 rps, RangeB: 50 rps, RangeC: 24 rps
Indoor fan 4th speed
Lo
Upper limit of compressor's speed RangeA: 50 rps, RangeB: 50 rps, RangeC: 24 rps
Indoor fan Adaptable to compressor speed
Auto, Me
Upper limit of compressor's speed RangeA: 50 rps, RangeB: 50 rps, RangeC: 30 rps
Indoor fan Adaptable to compressor speed
Hi
Upper limit of compressors speed
RangeA: 70 rps (SRK60: 80 rps), RangeB: 50 rps,
RangeC: 30 rps
Indoor fan
Adaptable to compressor speed
Note (1) Ranges A and B are as shown below.
Humidity(%)
60
68
Range A
Range B
73
Range C
2)
When this control has continued for more than 30 minutes continuously,the following wind direction control is per-
formed.
a)
When the vertical wind direction is set at other than the vertical swing,the flaps change to the horizontal po-
sition.
b)
When the horizontal wind direction is set at other than the horizontal swing,the louver changes to the vertical
position.
(iii) Reset condition
Humidity is less than 55%.
(b) SRK-ZR series
(i) Operating conditions
When the following conditions have been satisfied for more than 30 minutes after starting operation
1) Compressor's command speed is 28 rps (SRK100: 20 rps) or higher.
2) Detected value of humidity is 68% or higher.