EasyManuals Logo

Mitsubishi FDT71VH User Manual

Mitsubishi FDT71VH
202 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #51 background imageLoading...
Page #51 background image
-
50
-
'20 • PAC-SM-351
(10) Base heater ON/OFF output control (Option)
(a) Base heater ON conditions
Whenalloffollowingconditionsaresatised,thebaseheateristurnedON.
Outdoor air temperature (detected with Tho-A) is 3ºC or lower.
In the heating mode
When the compressor is turned ON
(b) Base heater OFF conditions
Wheneitheroneoffollowingconditionsissatised,thebaseheateristurnedOFF.
Outdoor air temperature (detected with Tho-A) is 5ºC or higher.
When the compressor stop has been detected for 30 minutes continuously
In the cooling or dehumidifying mode
Base heater ON
Base heater OFF
Outdoor air temperature (ºC)
53
(11) Manual defrost (Need to activate SW4-4) *For maintenance only.
When unit is operated with SW4-4 ON, defrost operation will be activated in every 12 minutes.
Caution! This function is used for maintenance only.
Long term operation with this function will damage the compressor.
(12) Limit the number of compressor start (Need to activate SW7-2)
Maximum number of compressor start is to be limited up to 6 times per hour.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi FDT71VH and is the answer not in the manual?

Mitsubishi FDT71VH Specifications

General IconGeneral
BrandMitsubishi
ModelFDT71VH
CategoryAir Conditioner
LanguageEnglish

Related product manuals