'22 • PAC-SM-412
-
10
-
(b) FDU, FDUA, FDE series
Return air temperature sensor [Thi-A (bytheremote control when theremotecontroltemperature sensor is enabled)]
controlstheindoortemperatureenvironmentsimultaneously.
(i)Operationisstartedinthecoolingmode.Whenthedierencebetweenthereturnairtemperatureandthesetting
temperatureis2°Corless,theindoorfanspeedisbroughtdownbyone.Thatspeedisretainedfor3minutesafter
changingtheindoorfanspeed.
(ii)Ifthereturnairtemperatureexceedsthesettingtemperatureby3°Cduringdehumidifyingoperation,theindoorfan
speedisraisedbyone.Thatspeedisretainedfor3minutesafterchangingtheindoorfanspeed.
(iii)IfthethermostatOFFisestablishedduringtheabovecontrol,theindoorfanspeedatthethermostatONisretainedso
farasthethermostatisturnedOFF.
(4) Timer operation
(a) RC-EXZ3A
(i) Sleep timer
Setthetimefromthestarttostopofoperation.Thetimecanbeselectedintherangefrom30to240minutes(inthe
unitof10-minute).
Note(1)Enablethe“Sleeptimer”settingfromtheremotecontrol.Ifthesettingisenabled,thetimeroperatesateverytime.
(ii)SetOFFtimerbyhour
Setthetimetostoptheunitafteroperation,intherangefrom1to12hours(intheunitofhour).
(iii) Set ON timer by hour
Setthetimetostarttheunitafterthestopof operation, in the range from 1 to 12 hours (in the unit of hour).It is
allowedalso to set simultaneously theindoortemperature,operationmode,air flow rate andwarm-upenabled/
disabled.
(iv)SetONtimerbyclock
Setthe time tostartoperation.Thetimecan besetintheunit of5-minute.Thissettingcanbeswitched onlyonce
ordaily.Itisallowedalsotosetsimultaneouslytheindoortemperature,operationmode,airowrateandwarm-up
enabled/disabled.
Note (1) It is necessary to set the clock to use this timer.
(v)SetOFFtimerbyclock
Setthetimetostopoperation.Thetimecanbesetintheunitof5-minute.Thissettingcanbeswitchedonlyonceor
daily.
Note (1) It is necessary to set the clock to use this timer.
(vi)Weeklytimer
SettheONorOFFtimerforaweek.Upto8patternscanbesetforaday.Theday-osettingisprovidedforholidays
and non-business days.
Note (1) It is necessary to set the clock to use the weekly timer.
(vii)
Combination of patterns which can be set for the timer operations
Í
Í
Í
Í
Í
Í Í
Í
Í
Í
Í
Í
Í
Í
Í
Í
Í
Í
Í
Í
Í
Í
Note (1) : Allowed Í: Not
Sleep timer
Sleep timer
Set OFF timer by hour
Weekly timer
Set ON timer by hour
Set OFF timer by clock
Set ON timer by clock
Set OFF timer by hour
Set ON timer by hour
Set OFF timer by clock
Set ON timer by clock
Weekly timer
(b) RC-E5
(i) Sleep timer
Setthedurationoftimefromthepresenttothetimetoturnotheair-conditioner.
Itcanbeselectedfrom10stepsintherangefrom“OFF1hourlater”to“OFF10hourslater”.AftertheSleeptimer
setting,theremainingtimeisdisplayedwithprogressoftimeintheunitofhour.
(ii)OFFtimer
TimetoturnOFFtheair-conditionercanbesetintheunitof10minutes.
(iii) ON timer
TimetoturnONtheair-conditionercanbesetintheunitof10minutes.Indoortemperaturecanbesetsimultaneously.
(iv)Weeklytimer
Timeroperation(ONtimer,OFFtimer)canbesetupto4timesadayforeachweekday.