'22 • PAC-SM-412
-
8
-
1.3 Operation control function by the indoor control
(1) Auto operation
(a)
If“Auto”modeisselectedbytheremotecontrol,theheatingandthecoolingareautomaticallyswitchedaccordingtothe
dierence between outdoor air temperature and setting temperature and the dierence between setting temperature and
returnairtemperature.(Whentheswitchingofcoolingmode
↔
heatingmodetakesplacewithin3minutes,thecompressor
does not operate for 3 minutes by the control of
3-minutetimer.)Thiswillfacilitatethecooling/heatingswitchingoperation
inintermediateseasonsandtheadaptationtounmannedoperationatstores,etc(ATMcornerofbank).
Notes(1)Temperaturerangeofswitchingcooling/heatingmodecanbechangedbyRC-EX3Afrom±1.0
-
±4.0.
(2)Room temperaturecontrolduringautocooling/autoheatingisperformed
accordingtothesettingroomtemperature.(DIFF:±1deg)
(3)Iftheindoorheatexchangertemperaturerisesto59°Corhigherduring
heatingoperation,itisswitchedautomaticallytocoolingoperation.In
addition,for1hourafterthisswitching,theheatingoperationisnot
performed,regardlessofthetemperatureshownatright.
+3-3
Cooling operation
Setting room temperature
Heating operation
Room temperature (detected with Thi-A) [°C]
5956
Heating operation stopped (cooling)
Heating OK
Indoor heat exchanger temperature (°C)
(b)Thefollowingautomaticcontrolsareperformedotherthan(a)above.
(i)Coolingorheatingoperationmodeisjudgedaccordingtotheconditionsofthe"JudgmentbasedonSettingtemperature+
CoolingselecttemperatureandIndoorreturnairtemperature"andthe"JudgmentbasedonOutdoortemperature".
1)
In"Settingtemperature-Coolingselecttemperature<Indoorreturnairtemperature"and"Outdoortemperature/Cooling<
Outdoorreturnairtemperature"
⇒
Operationmode:Cooling
2)
"Settingtemperature+Heatingselecttemperature>Indoorreturnairtemperature"and"Outdoortemperature/
Heating>Outdoorairtemperature"
⇒
Operationmode:Heating
3)Theoutdoorairtemperatureoftheabovejudgmentconditionsissampledatevery10minutes.
4)Intherangewheretheabovecoolingandheatingzonesareoverlapped
⇒
ForcedthermostatOFF
Indoor return air temperature (
°C
)
Outdoor air temperature (℃)
24 2612 14 16 18 28 3020 22
12
26
24
22
20
18
16
14
30
28
Heating
Cooling
Forced thermostat OFF
Forced thermostat
OFF
Forced
thermostat OFF
Outdoor temperature/Heating
Outdoor temperature/Cooling
Cooling select temperature Heating select temperature