'22 • PAC-SM-412
-
8
-
1.3 Operation control function by the indoor control
(1) Auto operation
(a)
If“Auto”modeisselectedbytheremotecontrol,theheatingandthecoolingareautomaticallyswitchedaccordingtothe
dierence between outdoor air temperature and setting temperature and the dierence between setting temperature and
returnairtemperature.(Whentheswitchingofcoolingmode
heatingmodetakesplacewithin3minutes,thecompressor
does not operate for 3 minutes by the control of
3-minutetimer.)Thiswillfacilitatethecooling/heatingswitchingoperation
inintermediateseasonsandtheadaptationtounmannedoperationatstores,etc(ATMcornerofbank).
Notes(1)Temperaturerangeofswitchingcooling/heatingmodecanbechangedbyRC-EX3Afrom±1.0
-
±4.0.
(2)Room temperaturecontrolduringautocooling/autoheatingisperformed
accordingtothesettingroomtemperature.(DIFF:±1deg)
(3)Iftheindoorheatexchangertemperaturerisesto59°Corhigherduring
heatingoperation,itisswitchedautomaticallytocoolingoperation.In
addition,for1hourafterthisswitching,theheatingoperationisnot
performed,regardlessofthetemperatureshownatright.
+3-3
Cooling operation
Setting room temperature
Heating operation
Room temperature (detected with Thi-A) [°C]
5956
Heating operation stopped (cooling)
Heating OK
Indoor heat exchanger temperature (°C)
(b)Thefollowingautomaticcontrolsareperformedotherthan(a)above.
 
(i)Coolingorheatingoperationmodeisjudgedaccordingtotheconditionsofthe"JudgmentbasedonSettingtemperature+
CoolingselecttemperatureandIndoorreturnairtemperature"andthe"JudgmentbasedonOutdoortemperature".
1)
In"Settingtemperature-Coolingselecttemperature<Indoorreturnairtemperature"and"Outdoortemperature/Cooling<
Outdoorreturnairtemperature"
Operationmode:Cooling
2)
"Settingtemperature+Heatingselecttemperature>Indoorreturnairtemperature"and"Outdoortemperature/
Heating>Outdoorairtemperature"
Operationmode:Heating
3)Theoutdoorairtemperatureoftheabovejudgmentconditionsissampledatevery10minutes.
4)Intherangewheretheabovecoolingandheatingzonesareoverlapped
ForcedthermostatOFF
Indoor return air temperature (
°C
)
Outdoor air temperature ()
24 2612 14 16 18 28 3020 22
12
26
24
22
20
18
16
14
30
28
Heating
Cooling
Forced thermostat OFF
Forced thermostat
OFF
Forced
thermostat OFF
Outdoor temperature/Heating
Outdoor temperature/Cooling
Cooling select temperature Heating select temperature
Setting temperature