(d) Fan control during cooling thermostat OFF
(i)FollowingfancontrolsduringthecoolingthermostatOFFcanbeselectedwiththeindoorfunctionsettingofthewired
remote control.
①
Low fanspeed
②
Setfanspeed(Factorydefault)
③
Intermittence
④
FanOFF
(ii)Whenthe“Lowfanspeed”isselected,thefollowingspeedisusedfortheindoorfans.
・ForDCmotor:ULo
(iii)Whenthe“Setfanspeed”isselected,itisoperatedwiththesetfanspeedalsointhethermostatOFFcondition.
(iv)Ifthe“Intermittence”isselected,followingcontrolsareperformed:
1)IfthethermostatisturnedOFFduringthecoolingoperation,theindoorfanmotorstops.
2)IndoorfanOFFisxedfor5minutes.Afterthe5minutes,theindoorfanisoperatedatULofor2minutes.Inthe
meantimethelouveriscontrolledatlevel.
3)AfteroperatingatULofor2minutes,theindoorfanmovestothestateof
1)above.
4) If the thermostat is turned ON, the fan starts operation at set fan speed.
5)WhenthecoolingthermostatisturnedOFF,theremotecontroldisplaysthetemperaturedetectedatthefanstopand
revisesthetemperaturelaterwhentheindoorfanchangesfromULotostop.
Byusingoperationdatadisplayfunctionatwirelessremotecontrol,thetempenatureasdisplayadandthevalueis
updatedincludingthefanstops.
6)WhenthecoolingthermostatisturnedONortheoperationischangedtoanothermode(includingstop),thiscontrol
isstoppedimmediately,andtheoperatingconditionisrestored.
(v)Whenthe“FanOFF”isselected,thefanontheindoorunitofwhichthethermostathasbeenturnedOFF,isturnedOFF.
Thesameoccursalsowhentheremotecontrolsensoriseective.
Astheoperationtime(TotalONtimeofON/OFFswitch)accumulatesto180hours
(1)
,“FILTERCLEANING”is
displayedontheremotecontrol.(Thisisdisplayedwhentheunitisintroubleandunderthecentralcontrol,regardlessof
ON/OFF.)
Notes(1)Timesettingfortheltersigncanbemadeasshownbelowusingtheindoorfunctionofwiredremotecontrol“Filtersign”.(Itissetatsetting1at
theshippingfromfactory.)
Filter sign setting
Setting 1
Setting 2
Setting 3
Setting 4
Function
Setting time: 180 hrs (Factory default)
Setting time: 600 hrs
Setting time: 1,000 hrs
Setting time: 1,000 hrs (Unit stop)
(2)
(2)After the setting time has elapsed, the “FILTERCLEANING” is displayed and, after operating for 24 hours further (counted also during the
stop), the unit stops.
(10) Compressor inching prevention control
(a) 3-minute timer
When the compressor has been stopped by the thermostat, remote control operation switch or anomalous condition, its
restartwillbeinhibitedfor3minutes.However,the3-minutetimerisinvalidatedatthepowerontheelectricpower
source for the unit.
(b) 3-minute forced operation timer
(i) Compressor will not stop for 3minutes after the compressor ON. However,it stops immediately when theunit is
stoppedbymeansoftheON/OFFswitchorwhenthethermostatisturnedOFFbythechangeofoperationmode.
(ii) IfthethermostatisturnedOFFduringtheforcedoperationcontrolofheatingcompressor,thelouverposition(with
theautoswing)isreturnedtothelevelposition.
Note(1)Thecompressorstopswhenithasenteredtheprotectivecontrol.
(9) Filter sign