(17) Plural unit control – Control of 16 units group by one remote control
(a) Function
Oneremotecontrolcancontrolagroupofmultiplenumberofunit(Max.16indoorunits).“Operationmode”which
is set by the remote control can operate or stop all units in the group one after another in the order of unit. No.
(1)
.
Thermostatandprotectivefunctionofeachunitfunctionindependently.
Note(1) UnitNo.issetbySW2ontheindoorunitcontrolPCB.UnitNo.settingbySW2isnecessaryfortheindoorunitonly.
(2) UnitNo.maybesetatrandomunlessduplicated,itshouldbebettertosetorderlylike0,1,2…,Ftoavoidmistake.
(b) Display to the remote control
(i) Centraloreachremotecontrolbasis,heatingpreparation
ThesmallestunitNo.amongtheoperatingunitsintheremotemode(orthecentermodeunlesstheremotemodeis
available)isdisplayed.
(ii) Inspectiondisplay,ltersign
Anyofunitthatstartsinitiallyisdisplayed.
(c) Confirmation of connected units
(i) IncaseofRC-EXZ3Aremotecontrol
Ifyoutouch the buttons intheorderof“Menu” → “Servicesetting”→“Service&Maintenance” → “Service
password”→“IUaddress”
on the TOP screen of remote control, the indoor units which are connected are displayed.
(ii) In case of RC-E5 remote control
Pressing“AIR CON No.”buttonontheremote control displaystheindoorunitaddress. If “▲”“▼”buttonis
pressedatthenext,itisdisplayedorderlystartingfromtheunitofsmallestNo..
(d) In case of anomaly
Ifanyanomalyoccursonaunitinagroup(aprotectivefunctionoperates),thatunitstopswiththeanomalousstop
but any other normal units continue to run as they are.
(e) Signal wiring procedure
Signal wiring between indoor and outdoor units should be made on each unit same as thenormal wiring. For the
groupcontrol,connecttheremotecontrolwiringtoeachindoorunitviaterminalblockfortheremotecontrol.
Connecttheremotecontrolwiringseparatelyfromthepowersourcecableorwiresofotherelectricdevices(AC220Vorhigher).
(18) Fan speed setting control
Whensucientairowratecannotbeobtainedfromtheindoorunitwhichisinstalledataroomwithhighceiling,the
airowratecanbeincreasedbychangingthefanspeed.Tochangethefanspeed,usetheindoorunitfunction“Fanspeed
setting”onthewiredremotecontrol.
-------
P-Hi1 - Hi
P-Hi1 - Me
P-Hi1 - Hi - Me
Standard
Setting1
Fan speed setting
Hi - Lo Hi - Me Only FDE (RC-EXZ3A)
Only FDT (RC-EXZ3A)
Only FDT, FDE (RC-EXZ3A)
Hi - Me - Lo
Hi - Lo Hi - MeHi - Me - Lo
P-Hi2 - P-Hi1 - Hi - Me
P-Hi1 - Hi
P-Hi1 - Me
P-Hi1 - Hi - Me
Except FDT, FDE (RC-EXZ3A)
P-Hi1 - P-Hi1 - Hi - Me
P-Hi2 - Hi - Me - Lo
Hi - Lo Hi - Me All series (RC-E5)Hi - Me - Lo
UH - Hi - Me - Lo
Hi - ULo Hi - Me Only FDT (RC-EXZ3A)Hi - Me - ULo
P-Hi2 - Hi - Me - ULo
Hi - Lo Hi - Me Except FDT, FDE (RC-EXZ3A)Hi - Me - Lo
P-Hi1 - Hi - Me - Lo
Indoor unit air flow rate setting
Series
(Wired remote control)
Fan speed
Setting2
P-Hi2 - Hi - Me - Lo
All series (RC-E5)
UH - Me UH - HiUH - Hi - Me
HIGH SPEED1, 2
UH - UH - Hi - Me
Only FDE (RC-EXZ3A)
Hi - Lo Hi - MeHi - Me - Lo
P-Hi1 - Hi - Me - Lo
Notes(1) FactorydefaultisStandard.
(2) Atthehot-startandheatingthermostatOFF,orother,theindoorfanisoperatedatthelowspeedofeachsetting.
(3) This function is not able to be set with wireless remote control or simple remote control (RCH-E3).
SW2:Forsettingof0–9,A–F
Remote control
Indoor unit
Signal wiring
between outdoor unit
and indoor units
Remote control wiring
R
0
123
F
4
Refrigerant piping