'22 • PAC-SM-412
-
19
-
(i) In case of “Level input” setting (Factory default)
InputsignaltoCnT-6orCnTAisOFF→ON……unitON
InputsignaltoCnT-6orCnTAisON→OFF……unitOFF
Operationisnotinverted.
ONON
OFF
OFF
OFF
ON
ON
ON
ON
Remote
control OFF
Remote
control ON
Remote
control OFF
Remote
control ON
OFF
OFF
OFF
CnT-6 or CnTA input
Unit A
Unit B
CnT-6 or CnTA input
Unit A
Unit B
Note (1) The latest operation has priority
Itisavailabletooperate/stopbyremotecontrolorcentralcontrol.
(b) Input for external control
Theexternalinputfortheindoorunitcanbeselectedfromthefollowinginput.
Input name Content
1 Run/Stop Referto[(20)(c)Remoteoperationinput]
2 Premission/Prohibition Referto[(21)Operationpermission/prohibition]
3 Cooling/Heating Refer to [(2
3
)Selectionofcooling/heatingexternalinputfunction]
4 Emergencystop Indoor/outdoorunitsstoptheoperation,and[E63]isdisplayed.
5 Settingtemperatureshift Settemperatureisshiftedby+2/-2°Cincooling/heating.
6 Forcedthermo-OFF Unitgoesthermoo.
7 Temporary stop Referto[(22)Temporarystopinput]
8 Silent mode Outdoorunitsilentmodeisactivated.
(ii) In case of “Pulse input” setting (Local setting)
ItiseectiveonlywhentheinputsignaltoCnT-6orCnTAischangedOFF→ON,andatthattimeunitoperation[ON/OFF]
isinverted.
ONON
OFF
OFF
OFF
ON
ON
ON
ON
Remote
control OFF
Remote
control ON
Remote
control OFF
Remote
control ON
ON
ON
OFF
OFF
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
CnT-6 or CnTA input
Unit A
Unit B
CnT-6 or CnTA input
Unit A
Unit B
(c) Remote operation input
(i) In case of multiple units (Max. 16 indoor units group) are connected to one wired remote control
WhentheR/Cfunctionsettingofwiredremotecontrolfor“Externalcontrolset”ischangedfrom“Individual(Factory
default)” to “ For allunits”, all units connected in one wired remote controlsystem can be controlled by external
operation input.
Ex. Indoor units =+①+②+③+……Ⓕ≦16units
0
XY
Wired remote control
Indoor unit
Signal &
Power
XY
123
123
XY
123
123
XY
123
123
XY
123
123
XY
123
123
Indoor unit
①
Outdoor unit
Outdoor unit Outdoor unit Outdoor unit Outdoor unit
Indoor unit
②
Indoor unit
③䚷
Indoor unit
Ⓕ
Cn
External
input
0
Refrigerant piping