'22 • PAC-SM-412
-
35
-
(d) Detail of opepation
(i)Changeoperationmodetocooling.
(ii)Thecompressorspeedisxedat40rps.
(iii)TheopeningoftheEEVisxedat470pulses.
1)Whenoutdoorairtemperature(TH2)anddischargepipetemperature(TH3)areinthecontrolrange(A)
Refrigerantejectioncontrol(2minutes)
Compressor stop (1 minute)
Normalheatingoperation
2)Whenoutdoorairtemperature(TH2)anddischargepipetemperature(TH3)areinthecontrolrange(B)
Refrigerantejectioncontrol(2minutes)
Compressor stop (1 minute)
Refrigerantejectioncontrol(2minutes)
Compressor stop (1 minute)
Refrigerantejectioncontrol(2minutes)
Afterstoppingthecompressorfor3minutes,startheatingoperation.
(-15,0)
TH2[°C]
TH3[°C]
Control range(A)
Control range(B)