'22 • PAC-SM-412
-
61
-
Error code
Remote control:
LED Green Red
Indoor
Content
None
Louver motor failure
(FDT, FDE series)
Keeps ashing
Stays OFF
1. Applicable model
5. Troubleshooting
FDT, FDE series only
Diagnosis Countermeasure
NO
YES
Is LM wiring
broken?
Is LM locked?
▲ Check at the indoor unit side.
LM: louver motor
Is the louver
operable with the remote
control?
YES
NO
Does the louver
operate at the power
on?
YES
NO
YES
NO
Operate after
waiting for more
than 1 minute.
Repair wiring.
Defective indoor unit
control PCB
Replace.
Replace LM.
Normal
Adjust LM lever and then
check again.
2. Error detection method
3.
Condition of error displayed
4. Presumable cause
Defective LM
LM wire breakage
Faulty indoor unit control
PCB
Note: