Error code
Remote control:
LED Green Red
Indoor
Content
None
Power source system error
(Power source to remote control)
Keeps ashing
3-time ash
1. Applicable model
5. Troubleshooting
All models
Diagnosis Countermeasure
Are there any
loose connection of remote
control wires?
Are remote
control wires broken or
short-circuited?
Is DC180V
between - of
CNW2?
Disconnect remote
control wires.
NO
Is DC15V or
higher detected between X-Y
of indoor unit terminal
block?
YES
YES
YES
YES
NO
NO
NO
Correct it.
Replace wires.
Replace remote control.
Defective indoor unit
power PCB
Replace.
Defective indoor unit
control PCB
Replace.
2. Error detection method
3 .
Condition of error displayed
4. Presumable cause
Remote control wire
breakage/short-circuit
Defective remote control
Malfunction by noise
Faulty indoor unit power PCB
Broken harness
Faulty indoor unit control PCB