E39
Discharge pipe
temperature sensor anomaly
1. Applicable model
5. Troubleshooting
All models
Diagnosis Countermeasure
Is the
discharge pipe
temperature sensor
connector connected
properly?
YES
Are the
characteristics
of discharge pipe
temperature
sensor
OK?
NO
For the characteristics of discharge pipe
temperature sensor, see the following graph.
YES
140120100806040200
0
100
50
[T 90
°C]
NO
Temperature-resistance characteristics
Temperature sensor resistance (k)
Temperature (°C)
(Broken wire)
(Short-circuit)
Correct connector.
Defective discharge pipe
temperature sensor
Replace.
Defective outdoor unit
PCB
Replace.
(Defective discharge pipe
temperature sensor input
circuit)
2. Error detection method
Detection of anomalously low
temperature (resistance) on
the discharge pipe temperature
sensor
3 .
Condition of error displayed
When the temperature sensor
detects -25 °C or lower for 5
seconds continuously within
10 minutes to 10 minutes 20
seconds after the compressor
ON, the compressor stops. After
3-minute delay, the compressor
starts again automatically, but
if this anomalous temperature
is detected 3 times within 40
minutes
4. Presumable cause
Defective outdoor unit PCB
Broken sensor harness or
temperature sensing section
(Check molding.)
Disconnected wire connection
(connector)
Note:
Error code
Remote control:
LED Green Red
Content
Indoor
Stays OFF
Keeps flashing
'22 • PAC-SM-412
-
85
-