A - 3
CAUTION
! Use the inverter under the following environmental conditions:
Ambient
temperature
-10°C to + 50°C (14°F to 122°F) (non-freezing)
Ambient humidity 90%RH or less (non-condensing)
Storage
temperature
-20°C to +65°C (-4°F to 149°F) *
Ambience
Indoors (free from corrosive gas, flammable gas,
oil mist, dust and dirt)
Environment
Altitude,
vibration
Maximum 1000m (3280.80feet) above sea level
for standard operation. After that derate by 3% for
every extra 500m (1640.40feet) up to 2500m
(8202.00feet) (91%).
5.9m/s
2
or less (conforming to JIS C0911)
*Temperatures applicable for a short time, e.g. in transit.
(2) Wiring
CAUTION
! Do not fit capacitive equipment such as power factor correction capacitor,
radio noise filter or surge suppressor to the output of the inverter.
! The connection orientation of the output cables U, V, W to the motor will
affect the direction of rotation of the motor.
(3) Trial run
CAUTION
! Check all parameters, and ensure that the machine will not be damaged by a
sudden start-up.
(4) Operation
WARNING
! When you have chosen the retry function, stay away from the equipment as it
will restart suddenly after an alarm stop.
! The [STOP] key is valid only when the appropriate function setting has been
made. Prepare an emergency stop switch separately.
! Make sure that the start signal is off before resetting the inverter alarm. A
failure to do so may restart the motor suddenly.
! The load used should be a three-phase induction motor only. Connection of
any other electrical equipment to the inverter output may damage the
equipment.
! Do not modify the equipment.