* Rank 1=Lb, Rank 2=La, Rank 3=Mi, Rank 4=Hi, Rank 5=HH, Rank 6=SH
4 Mildew Guard mode
(a) Alternately activates/deactivates compressor or blower according to current humidity/time. (Fan rank is as shown in 2)
(b) Operates dehumidifier when Mildew guard mode is activated or every 24 hours after activation.
(c) Dehumidifier is deactivated when the following parameters are breached. (Compressor and blower stop)
•2 hours of below 40% elapses and below 35% is detected.
•4 hours of below 50% elapses and below 45% is detected.
* However, if the humidity rises above the given levels for more than 3 minutes, the accumulated time returns to zero.
(d) If the humidity rises to 75% after deactivation, the dehumidifier automatically operates until the humidity is brought down to 65%.
(e) If 24 hours elapse from the time the unit was turned on, all accumulated time counts for all humidity levels are reset.
14
<Operation Control>
1 Humidity set operation
(a) Compressor and blower fan operation will switch by current humidity and set temperature.
2 Specifications shared at all operation modes
(a) Dehumidifying will not start for about 2 seconds when turning the operation power on with the swing stopped. (However, humidifying
will begin immediately when pressing the swing louvre switch within 2 seconds of turning the power on.)
(b) The compressor and blower fan will operate for about 7 minutes after turning on the operation switch or activating the compressor,
regardless of humidity or temperature levels.
3 Low, Low Temp, Mildew Guard, Air Purifier, Laundry