 56 
-
 '15 • SRK-T-172
 
 
Trouble of outdoor unit
[Compressor malfunction of 
insufficient gas (refrigerant)]
Does compressor operation?
Is capacitor for compressor normal?
Replace compressor.
Insufficient gas
Is refrigerant amount normal?
Is connector for compressor connection 
good?
Does trouble persist after charging gas?
Clogged capillary tube or strainer, 
etc.
Replace capacitor for compressor.
Correct connection
Check if there are any places where 
gas is leaking
YES
YES
NO NO
NO
NO
NO
YES
YES
YES
(8)  Checking the indoor electrical equipment
(a)  Indoor PCB check procedure
Is there voltage at power source?
 
      (AC 220/230/240V)
Replace PCB
 
Inspect  power  source. 
If the package components
are not damaged, replace the
fuse and perform an operation
check again.
Is the fuse burnt out? (3.15 A)
NO
YES
NO
YES
(7)  Phenomenon observed after shortcircuit, wire breakage on sensor
(a)  Indoor unit
     
Phenomenon
Sensor
   
Shortcircuit
   
Broken wire
 
Cooling
  Release of continuous compressor operation command
                 
 
Cooling
  System can be operated normally.
Operation 
mode
Continuous compressor operation command is not released.
(Room temperature sensor error.)
Continuous compressor operation command is not released. 
(Anti-frosting, heat exchanger sensor error.)
Heat exchanger 
sensor
Room temperature 
sensor