77
-
(g) Heating overload protective control
(i) Indoor fan speed
1) Operating conditions
2) Detail of operation
3) Reset conditions
(ii) Outdoor unit side
(i) Operating conditions:
(ii) Detail of operation:
(h) Heating low outdoor temperature protective control
(iii) Reset conditions:
-10 -8 -2 2
Lower limit 45 rps
Lower limit 40 rps
Normal operation
Outdoor air temperature(°C
• Model SRK50
• Models SRK20 ~ 35
(i)
ࠉ
Operating conditions: When the outdoor air temperature (TH2) is lower than 4ºC or 13ºC or higher continues for 30
seconds while the compressor command speed is other than 0 rps.
(ii)ࠉDetail of operation: The lower limit compressor command speed is change as shown in the figure belo.
Lower limit 29 rps
Normal operation
46
Outdoor air temperature(°C)
Model SRK50
ABCD
RPSmin < 40
40
<
=
RPSmin < 80
80
<
=
RPSmin < 90
90
<
=
RPSmin < 102
102
<
=
RPSmin
49
53
41
53 - 47
47 - 41
53
57
45
57 - 51
51 - 45
55
59
47
59 - 53
53 - 47
58
62
51
58
51
1)
2)
The indoor fan speed is stepped up by 1 speed step. (Upper limit 10th speed)
When the outdoor air temperature (models SRK20, 25, 35 : TH3 ; models SRK50, 60 : TH2) is 17°C or higher continues
for 30 seconds while the compressor speed other than 0 rps.
The outdoor air temperature (
models SRK20, 25, 35 : TH3 ; models SRK50, 60 : TH2
) is lower than 16°C.
1) Operating conditions
2) Detail of operation
3) Reset conditions
10 11 19 20
Normal operation
Protective control ON1
Protective control ON2
Outdoor air temperature(°C)
• Model SRK50
a)
b)
c)
d)
The lower limit of compressor speed is set to 25 (30) rps or 35 (40) rps and even if the calculated result
becomes lower than that after fuzzy calculation, the speed is kept to 25 (30) rps or 35 (40) rps. However,
when the thermostat OFF, the speed is reduced to 0 rps.
fan speed is
rps.
1) Operating conditions
2) Detail of operation
When the outdoor air temperature (TH2) is 11ºC or higher continues for 30 seconds while the compressor speed other than 0 rps.
a)
b)
c)
d)
Taking the upper limit of compressor speed range at 78 rps, if the output speed obtained with the fuzzy calculation
exceeds the upper limit, the upper limit value is maintained.
The lower limit of compressor speed is set to 30 rps and even if the calculated result becomes lower than that after
fuzzy calculation, the speed is kept to 30 rps. However, when the thermostat OFF, the speed is reduced to 0 prs.
rps.
3) Reset conditions
30
Protective
control
ON1
ON2
Item
Compressor speed
Low limit
30 rps
30 rps
Upper limit
78 rps
51 rps
When the outdoor air temperature (models SRK20, 25, 35 : TH3 ; models SRK50, 60 : TH2) is 13°C or higher continues
for 30 seconds while the compressor speed other than 0 rps.
The outdoor air temperature (TH3) is lower than 11°C.
The outdoor air temperature (TH2) is lower than 10°C.
Outdoor fan speed
It depends on compressor speed
2nd
Taking the upper limit of compressor speed at 90 rps or 50 (75) rps, if the output speed obtained with the
fuzzy calculation exceeds the upper limit, the upper limit value is maintained.
3rd (models SRK50, 60 : 2nd) speed.
11 13 16 17
Upper 90 rps
Lower 25 (30) rps
OFF
Lower 35 (40) rps
Outdoor air temperature (°C)
Note(1) Values in ( ) are for the models SRK50, 60.
(i) Operating conditions
When the outdoor air temperature (models SRK20, 25, 35 : TH3 ; models SRK50, 60 : TH2) is lower than 4℃ or
higher continues for 30 seconds while the compressor speed is other than 0 rps.
(ii) Detail of operation
The lower limit compressor speed is change as shown in the figure below.
(h) Heating low outdoor temperature protective control
(iii) Reset conditions
When either of the following condition is satisfied.
1) The outdooe air temperature (models SRK20, 25, 35 : TH3 ; models SRK50, 60 : TH2) becomes 6℃.
2) The compressor speed is 0 rps.
Note(1) Values in ( ) are for the models SRK50, 60.
-4-6-8-10-12 -2 4
Lower limit 32 (40) rps
Lower limit 45 rps
Lower limit 55 rps
Lower limit 20 (35) rps
Normal operation
Outdoor air temperature (°C)
6
3) Reset conditions
The outdoor air temperature (models SRK20, 25, 35 : TH3 ; models SRK50, 60 : TH2) is lower than 11°C.