-
 61 
-
 
CAUTION
6.  Repair to intrinsically safe components
•  Do not apply any permanent inductive or 
capacitance loads to the circuit without ensuring 
that this will not exceed the permissible voltage and 
current permitted for the equipment in use.
• 
Intrinsically 
safe components are the only types that 
can be worked on while live in the presence of a 
flammable atmosphere
• 
The test apparatus shall be at the correct rating.
•
 
Replace components only with parts specified by
the manufacturer
.
•  Other parts may result in the ignition of refrigerant 
in the atmosphere from a leak.
7. 
Cabling
•  Check that cabling will not be subject to wear, 
corrosion, excessive pressure, vibration, sharp 
edges or any other adverse environmental effects. 
The check shall also take into account the effects 
of aging or continual vibration from sources such as 
compressors or fans.
8. 
Detection of flammable refrigerant
•  Under no circumstances shall potential sources of 
ignition be used in the searching for or detection of 
refrigerant leaks.
• 
A
 halide torch (or any other detector using a naked 
flame) shall not be used
9. 
Leak detection methods
•  Electronic leak detectors may be used to detect 
refrigerant leaks but, in the case of flammable
refrigerants, the sensitivity may not be adequate, or 
may need re-calibration. (Detection equipment shall 
be calibrated in a refrigerant-free area.)
•  Ensure that the detector is not a potential source of 
ignition and is suitable for the refrigerant used.
• 
Leak detection equipment shall be set at a 
percentage of the LFL
 of the refrigerant and shall 
be calibrated to the refrigerant employed, and the 
appropriate percentage of gas (25 % maximum) is 
confirmed
• 
Leak detection fluids are suitable for use with most
refrigerants but the use of detergents containing 
chlorine shall be avoided as the chlorine may 
react with the refrigerant and corrode the copper 
pipe-work.
•
 
If a leak is suspected, all naked flames shall be
removed/extinguished.
•
 
If a leakage of refrigerant is found which requires 
brazing, all of the refrigerant shall be recovered 
from the system, or isolated (by means of shut of
f 
valves) in a part of the system remote from the 
leak.
• 
For appliances containing flammable refrigerants,
oxygen free nitrogen (OFN) shall then be purged 
through the system both before and during the 
brazing process.
10. Removal and evacuation
• 
When breaking into the refrigerant circuit to make 
repairs – or for any other purpose – conventional 
procedures shall be used. However
, for flammable
refrigerants it is important that best practice is 
followed since flammability is a consideration
• 
The following procedure shall be adhered to:
– remove refrigerant;
– purge the circuit with inert gas;
– evacuate;
– purge again with inert gas;
– open the circuit by cutting or brazing.
•
 
The refrigerant charge shall be recovered into the 
correct recovery cylinders.
•
 
For appliances containing flammable refrigerants,
the system shall be “flushed” with OFN to render
the unit safe. 
This process may need to be repeated several 
times.
•
 
Compressed air or oxygen shall not be used for 
purging refrigerant systems.
•
 
For appliances containing flammable refrigerants,
flushing shall be achieved by breaking the vacuum
in the system with OFN and continuing to fill until
the working pressure is achieved, then venting to 
atmosphere, and finally pulling down to a vacuum  
This process shall be repeated until no refrigerant 
is within the system.
•
 
When the final OFN charge is used, the system
shall be vented down to atmospheric pressure to 
enable work to take place. 
This operation is absolutely vital if brazing 
operations on the pipe-work are to take place.
•
 
Ensure that the outlet for the vacuum pump is not 
close to any ignition sources and that ventilation is 
available.
11. Charging procedures
• 
In addition to conventional charging procedures, the 
following requirements shall be followed.
– Ensure that contamination of dif
ferent refrigerants 
does not occur when using charging equipment. 
Hoses or lines shall be as short as possible to 
minimise the amount of refrigerant contained in 
them.
– Cylinders shall be kept upright.
– Ensure that the refrigeration system is earthed 
prior to charging the system with refrigerant.
– Label the system when charging is complete (if 
not already).
– Extreme care shall be taken not to overfill the
refrigeration system.
•  Prior to recharging the system, it shall be pressure-
tested with the appropriate purging gas.
• 
The system shall be leak-tested on completion of 
charging but prior to commissioning.
•
 
A
 follow up leak test shall be carried out prior to 
leaving the site.
12. Decommissioning
• 
Before carrying out this procedure, it is essential 
that the technician is completely familiar with the 
equipment and all its detail. 
•
 
It is recommended good practice that all 
refrigerants are recovered safely
. 
• 
Prior to the task being carried out, an oil and 
refrigerant sample shall be taken in case analysis is 
required prior to re-use of reclaimed refrigerant.
•
 
It is essential that electrical power is available 
before the task is commenced.
a) Become familiar with the equipment and its 
operation.
b) Isolate system electrically
.
c) Before attempting the procedure ensure that:
– mechanical handling equipment is available, if 
required, for handling refrigerant cylinders;
– all personal protective equipment is available and 
being used correctly;
– the recovery process is supervised at all times by 
a competent person;
– recovery equipment and cylinders conform to the 
appropriate standards.
d) 
Pump down refrigerant system, if possible.
e)
  
If a vacuum is not possible, make a manifold so 
that refrigerant can be removed from various parts 
of the system.
f)
   
Make sure that cylinder is situated on the scales 
before recovery takes place.
g)
  
Start the recovery machine and operate in 
accordance with manufacturer
’s instructions.
h)  
Do not overfill cylinders. (No more than 80 %
volume liquid charge).
i)
   
Do not exceed the maximum working pressure of 
the cylinder
, even temporarily.
j)   When the cylinders have been filled correctly
and the process completed, make sure that the 
cylinders and the equipment are removed from site 
promptly and all isolation valves on the equipment 
are closed off.
k) Recovered refrigerant shall not be charged into 
another refrigeration system unless it has been 
cleaned and checked.
13. Labelling
• 
Equipment shall be labelled stating that it has been 
de-commissioned and emptied of refrigerant. 
The 
label shall be dated and signed.
• 
For appliances containing flammable refrigerants,
ensure that there are labels on the equipment 
stating the equipment contains flammable
refrigerant.
14. Recovery
• 
When removing refrigerant from a system, either for 
servicing or decommissioning, it is recommended 
good practice that all refrigerants are removed 
safely
.
•  When transferring refrigerant into cylinders, ensure 
that only appropriate refrigerant recovery cylinders 
are employed.
• 
Ensure that the correct number of cylinders for 
holding the total system charge are available.
•
  All cylinders to be used are designated for 
the recovered refrigerant and labelled for that 
refrigerant (i.e. special cylinders for the recovery of 
refrigerant).
• 
Cylinders shall be complete with pressure relief 
valve and associated shut-of
f valves in good 
working order.
• 
Empty recovery cylinders are evacuated and, if 
possible, cooled before recovery occurs.
•
 
The recovery equipment shall be in good working 
order with a set of instructions concerning the 
equipment that is at hand and shall be suitable 
for the recovery of all appropriate refrigerants 
including, when applicable, flammable refrigerants
•
 
In addition, a set of calibrated weighing scales shall 
be available and in good working order
.
• 
Hoses shall be complete with leak-free disconnect 
couplings and in good condition.
•
 
Before using the recovery machine, check that it 
is in satisfactory working order
, has been properly 
maintained and that any associated electrical 
components are sealed to prevent ignition in the 
event of a refrigerant release. 
Consult manufacturer if in doubt.
•
 
The recovered refrigerant shall be returned to the 
refrigerant supplier in the correct recovery cylinder
, 
and the relevant Waste Transfer Note arranged. 
Do not mix refrigerants in recovery units and 
especially not in cylinders.
•
 
If compressors or compressor oils are to be 
removed, ensure that they have been evacuated to 
an acceptable level to make certain that flammable
refrigerant does not remain within the lubricant.
•
 
The evacuation process shall be carried out prior to 
returning the compressor to the suppliers.
•
 
Only electric heating to the compressor body shall 
be employed to accelerate this process.
•
  When oil is drained from a system, it shall be 
carried out safely.
15. Other safety precautions
• 
A
 brazed, welded, or mechanical connection shall 
be made before opening the valves to permit 
refrigerant to flow between the refrigerating system
parts.
•  Flammable refrigerant used, refrigerant tubing 
protected or enclosed to avoid mechanical damage 
(IEC/EN 60335-2-40/A1).
• 
T
ubing protected to extent that it will not be handled 
or used for carrying during moving of product (IEC/
EN 60335-2-40/A1).
• 
Flammable 
refrigerant used, low temperature solder 
alloys, such as lead/tin alloys, not acceptable for 
pipe connections (IEC/EN 60335-2-40/A1).
• 
When there is flare connection, it must be installed
outdoor
.