 83 
-
When a heat exchanger sensor 1 wire disconnection is detected while 
operation is stopped. (If a temperature of –28ºC or lower is detected for 
15 seconds, it is judged that the wire is disconnected.) 
(Not displayed during operation.)
When a room temperature sensor wire disconnection is detected while 
operation is stopped. (If a temperature of –45ºC or lower is detected for 
15 seconds, it is judged that the wire is disconnected.) 
(Not displayed during operation.)
• Broken heat exchanger sensor 
1 wire, poor connector 
connection
• Indoor PCB is faulty
• Broken room temperature 
sensor wire, poor connector 
connection
• Indoor PCB is faulty
Heat exchanger 
sensor 1 error
Room
temperature
sensor error
When conditions for turning the indoor unit’s fan motor on exist during air-
conditioner operation, an indoor unit fan motor speed of 300 min
-1
 or lower is 
• Defective fan motor, poor
connector connection
Indoor fan 
motor error
 –55ºC or lower is detected for 5 seconds continuously 3 times within 
40 minutes after initial detection of this anomalous temperature.
Or  –55ºC or lower is detected for within 20 seconds after power ON. 
(The compressor is stopped.)
 –55ºC or lower is detected for 5 seconds continuously 3 times within 
40 minutes after initial detection of this anomalous temperature.
Or  –55ºC or lower is detected for within 20 seconds after power ON. 
(The compressor is stopped.)
• Broken heat exchanger sensor 
wire, poor connector 
   connection
• Outdoor PCB is faulty
Outdoor heat 
exchanger
sensor error
–25ºC or lower is detected for 5 seconds continuously 3 times within 40 
minutes after initial detection of this anomalous temperature.
(The compressor is stopped.)
• Broken discharge pipe sensor 
wire, poor connector 
connection
• Outdoor PCB is faulty
Discharge pipe 
sensor error
The compressor output current exceeds the set value during compressor 
start.
(The air-conditioner stops.)
• 
,
Compressor locking, open phase
on compressor output, short 
circuit on power transistor
service valve is closed
Current cut
gency stop caused by trouble in the outdoor unit, When there is an emer
or the input current value is found to be lower than the set value.
 (The air-conditioner stops.)
When the power transistor is judged breakdown while compressor 
starts.
(The compressor is stopped.)
• Broken compressor wire
• Compressor blockage
Trouble of 
outdoor unit
When the value of the discharge pipe sensor exceeds the set value. 
(The air-conditioner stops.)
• Gas shortage, defective 
discharge pipe sensor, service 
valve is closed
Over heat of 
compressor
When there is no signal between the indoor PCB and outdoor PCB for 
10 seconds or longer (when the power is turned on), or when there is no 
signal for 7 minute 35 seconds or longer (during operation) 
(The compressor is stopped).
• Defective power source,
Broken signal wire, defective 
indoor/outdoor PCB
Error of signal 
transmission
If the compressor motor’s magnetic pole positions cannot be correctly 
detected when the compressor starts. 
(The air-conditioner stops.)
• Defective compressor
• Open phase on compressor
• Defective outdoor PCB
• Service valve is closed.
• Refrigerant is insufficient
Rotor lock
When the outdoor unit’s fan motor speed continues for 30 seconds or 
longer at 75 
min
-1
 or lower. (3 times) 
(The air-conditioner stops.)
• Defective fan motor, poor
connector connection
Outdoor fan 
motor error
Indoor unit display panel
Description
of trouble
Cause Display (flashing) condition
When the compressor speed is lower than the set value and the current 
safe has operated. 
(The compressor stops)
• Overload operation
• Overcharge
• Compressor locking
Current safe 
stop
• Broken power transistor
Power 
transistor
error
When a heat exchanger sensor 2 wire disconnection is detected while 
operation is stopped. (If a temperature of –28ºC or lower is detected for 
15 seconds, it is judged that the wire is disconnected.) 
(Not displayed during operation.)
• Broken heat exchanger sensor 
2 wire, poor connector 
connection
• Indoor PCB is faulty
Heat exchanger 
sensor 2 error
When the value of the outdoor heat exchanger sensor exceeds the set 
value.
• 
Overload operation, overcharge
• Broken outdoor heat exchange 
sensor wire
• Service valve is closed
Cooling high 
pressure
protecton
When the wrong voltage connected for the power source.
When the outdoor PCB is faulty.
• Defective active filter
Active filter 
voltage error
When refrigeration cycle system protective control operates.
Refrigeration
cycle system 
protective 
control
ON
ON
ON
2-time
flash
4-time
flash
1-time
flash
2-time
flash
5-time
flash
6-time
flash
2-time
flash
7-time
flash
TIMER
light
3-time
flash
4-time
flash
ON
Keeps
flashing
ON
ON
1-time
flash
2-time
flash
6-time
flash
Keeps
flashing
Keeps
flashing
ON
ON
ON
ON
2-time
flash
ON
RUN
light
ON
ON
3-time
flash
ON
5-time
flash
7-time
flash
Stays
OFF
Keeps
flashing
E 16
• Broken outdoor air temp. 
sensor wire, poor connector 
connection
• Outdoor PCB is faulty
Outdoor air 
temperature
sensor error
1-time
flash
Keeps
flashing
E 38
E 37
E 39
E 42
E 59
E 36
E 5
E 60
E 47
E 48
E 35
Actuation of limit switch
• Defective limit switch
• Defective suction panel set
• Defective indoor contro PCB
Limit switch
error
—
E 58
E 51
Wired
(2)
remote
control
display
E 57
—
—
—
(5) Self-diagnosis table
measured for 30 seconds or longer. (The air-conditioner stops.)
air-conditioner
air-conditioner
air-conditioner
air-conditioner
The wired remote control wire Y is open. The wired remote 
control wires X and  Y are reversely connected. Noise is penetrating 
the wired remote control lines.  The wired remote control or indoor 
PCB is faulty. (The communications circuit is faulty.)
• Broken wired remote control
wire, defective indoor PCB
Error of wired 
remote control 
wiring
—
—
E 1