Appendix
01/02 AWB8230-1413GB
174
PNU Function Units WE Page Setpoint
C001 Function of digital input 1
01: REV, anticlockwise operation
02: FF1, first fixed frequency input
03: FF2, second fixed frequency input
04: FF3, third fixed frequency input
05: FF4, fourth fixed frequency input
06: JOG, jog mode
07: DB, DC braking
08: SET, second parameter set
09: 2CH, second time ramp
11: FRS, controller inhibit
12: EXT, external fault
13: USP, unattended start protection
14: CS, heavy mains starting
15: SFT, parameter protection
16: AT, analog input selection
18: RST, reset
20: STA, three-wire control start signal
21: STP, three-wire control stop signal
22: STA, three-wire control direction
23: PID, activate PID control
24: PIDC, reset integral component of PID control
27: UP, remote access, acceleration
28: DWN, remote access, deceleration
29: UDC, reset frequency with remote control
31: OPE, setpoint value through keypad
32 to 38: Bitwise fixed frequencies
39: OLR, change over current limit
NO: no, no function
–18 65
C002 Function of digital input 2 (values a PNU C001) 16 65
C003 Function of digital input 3 (values a PNU C001) 03 65
C004 Function of digital input 4 (values a PNU C001) 02 65
C005 Function of digital input 5 (values a PNU C001) 01 65
C011 Digital input 1
00: Make contact
01: Break contact
–00 66
C012 Digital input 2 (values a PNU C011) 00 66
C013 Digital input 3 (values a PNU C011) 00 66
C014 Digital input 4 (values a PNU C011) 00 66
C015 Digital input 5 (values a PNU C011) 00 66
C019 Digital input FW (values a PNU C011) 00 66
C021 Signal to relay output K23-K24
00: RUN signal
01: FA1, frequency reached
02: FA2, frequency exceeded
03: OL, Overload
04: OD, PID deviation exceeded
05: AL, fault
06: FA3, frequency reached (1)
08: IP, mains failure, immediate stop
09: UV, undervoltage
11: ONT, mains On time exceeded
12: RNT, running time exceeded
13: THM, motor thermal overload
–01 94