v1.05
6.26.09
- 39 -
Monico
Id
PID Description Modbus
Address
Manual Remarks
60 Diagnostic Status Summary 30062 Bits 2-1: 0=None, 1=Level 1 Warning, 2=Level2 Warning,
3=Level 3 Warning. Bit 3&4 not used. Bit 5: 0=No logged
events, 1=At least 1 logged event. Bit 6 not used. Bit7: 0=No
logged diag., 1=At least 1 logged diag. Bit8: 0=No active
diag. 1=At least 1 active diag.
69 General Alarm Output Status/Override (Marine Only) 30071 (This can be written to) Bit 8: 1=Override, 0=Normal. Bit 1:
0=Output is OFF, 1=Output is ON
99 Engine Status 30102 Bit 4: 1=Fuel injection disabled, 0=No injection disabled.
Bit5: 1=E-stop shutdown, 0=No E-stop shutdown. Bit 1:
1=No Engine Speed, 0=Engine Speed
116 GSC Relay Status 30119 Organized by bit pairs where for each pair 0=Off/de-
energized, 1=On/energized, 3=Relay not installed: Bits
2,1=Air Shutoff Relay. Bits 4,3=Fuel Control Relay. Bits
6,5=Crank Terminate Relay. Bits 8,7=Starter Motor Relay.
Bits 10,9=Genset Fault Relay. Bits 12,11=Run Relay. Bits
14,13=Program Spare Relay. Bits 16,15=Electronic Governor
Relay.
117 GSC Relay Control 30120 (only bits 16-13 are write able) Organized by bit pairs where
for each pair 0=Off/de-energized, 1=On/energized, 3=Relay
not installed, keep same state: Bits 2,1=Air Shutoff Relay.
Bits 4,3=Fuel Control Relay. Bits 6,5=Crank Terminate
Relay. Bits 8,7=Starter Motor Relay. Bits 10,9=Genset Fault
Relay. Bits 12,11=Run Relay. Bits 14,13=Program Spare
Relay. Bits 16,15=Electronic Governor Relay.
121 GSC Alarm Status
30124
Organized by bit pairs where for each pair 0=Alarm Off,
1=Alarm On, 3=Not Available: Bits 2,1=High Coolant Temp.
Bits 4,3=Low Coolant Temp. Bits 6,5=Low Oil Psi. Bits
8,7=Eng Control Switch not in Auto or Manual. Bits
10,9=High Oil Temp. Bits 12,11=Eng Control Alarm. Bits
14,13=Not used. Bits 16,15=Undefined.
122 GSC Shutdown Status 30125 Organized by bit pairs where for each pair 0=Shutdown
Inactive, 1=Shutdown Active, 3=Not Available: Bits
2,1=Diag Code. Bits 4,3=Coolant Loss. Bits 6,5=Emg Stop.
Bits 8,7=Spare Fault. Bits 10,9=High Coolant Temp. Bits
12,11=Low Oil Psi. Bits 14,13=Overcrank. Bits
16,15=Overspeed.
123 GSC Spare Fault Alarm Status 30126 Organized by bit pairs where for each pair 0=Alarm Off,
1=Alarm On, 3=Not Available: Bits 2,1=Spare Fault 1. Bits
4,3=Spare Fault 2. Bits 6,5=Spare Fault 3. Bits 8,7=Spare
Fault 4. 16-9=Undefined.
124 GSC Spare Fault Shutdown Status 30127 Organized by bit pairs where for each pair 0=Shutdown
Inactive, 1=Shutdown Active, 3=Not Available: Bits
2,1=Spare Fault 1. Bits 4,3=Spare Fault 2. Bits 6,5=Spare
Fault 3. Bits 8,7=Spare Fault 4. 16-9=Undefined.
146 Generator Set Control Output Status (GSC+ only) 30149 Organized by bit pairs where for each pair 0=Off/de-
energized, 1=On/energized, 2=Output Fault, 3=Output not
installed: Bits 2,1=Close Breaker Output. Bits 4,3=Kilowatt
Relay Control Output
147 Generator Set Shutdown Status - Extension #1 30150 Organized by bit pairs where for each pair 0=Shutdown
Inactive, 1=Shutdown Active, 3=Not Available: Bits
13,14=Engine Control Shutdown. Bits 15,16=High Engine
Oil Temp.
254 Active Warning Summary Status 30285 Bit 16=Warning Level 1, Bit 15=Warning Level 2, Bit
14=Warning Level 3 (bit value: 0=INACTIVE, 1=ACTIVE)