6 TDS3 · TDS3-L
Example 2: Master with Slave Units
The remote interface feature oers the opon of lower cost 2-way or mul-way switching by
connecng up to ve slave switches to a single TDS3 master unit. Unlike parallel wiring (Example 1),
this method retains full control from any switch locaon, and does not increase the minimum load
requirement. The master unit controls the ming cycle and switches the load, and any of the slave
switches will funcon idencally to that on the master unit.
Each slave switch may be either a TDS-S slave unit (which provides an idencal touchsensive
buon) or an ordinary normally-open mechanical switch (such as a pushbuon or retracve rocker).
Referring to the steps under Installaon, connect as follows.
• TDS-S: Use 3-core mains-rated cable and connect as shown below. Figure 5 illustrates a typical
wiring example using two TDS-S slave units; Figure 6 represents the same conguraon as
applied to a typical ceiling rose lighng circuit.
• Other switches: Use 2-core mains-rated cable and connect to the R+ and R- terminals only
(polarity does not maer); do not use the V+ terminal.
Figure 6 Typical ceiling rose plan using two TDS-S slave units
The slave switch connecons are referenced to the mains supply of the unit, and are therefore not
safe to touch when the unit is powered. All switches and cables must be rated for mains voltages.