OPERATING AND MAINTENANCE MANUAL
Chapter 7 - Electronic controller
TAEevo Tech 015÷802 60 Hz UL
98
The data in this manual are not binding and they can be modified by the manufacturer without notice. Reproduction of this manual is strictly prohibited
ENGLISH
EN
FS13 C Time lag between two Anti-Legionella production cycles. If the
value is set to 0 the function is disabled.
0 250 by Hours
FS14 C Anti-Legionella setpoint
Used to set the Anti-Legionella working setpoint
FS15 FS16 °C
°F
Dec
Int
FS15 C Anti-Legionella setpoint minimum value
Establishes the minimum limit that can be utilised to set the Anti-
Legionella setpoint
-50.0
-58
FS14 °C
°F
Dec
Int
FS16 C Anti-Legionella setpoint maximum value
Establishes the maximum limit that can be utilised to set the Anti-
Legionella setpoint
FS14 110.0
230
°C
°F
Dec
Int
FS17 C Anti-Legionella activation time 0 24.00 by Hours 10 Min
FS18 C Anti-Legionella activation day:
1= Sunday ……. 7= Saturday
07
FS19 C Holding time in Anti-Legionella production 1 250 Min
FS20 C Heating elements switch-off band in Anti-Legionella 0.1
0
25.0
45
°C
°F
Dec
Int
FS21 C Free cooling operation enabling differential 0.1
0
25.0
45
°C
°F
Dec
Int
FS22 C Free cooling operation hysteresis 0.1
0
25.0
45
°C
°F
Dec
Int
FS23 C Water setpoint for solar panels integration
Used to set the working setpoint of the solar panels
FS25 FS26 °C
°F
Dec
Int
FS24 C Solar panels integration operation band 0.1
0
25.0
45
°C
°F
Dec
Int
FS25 C Solar panels minimum water set
Establishes the minimum limit that can be utilised to set the solar
panels setpoint
-50.0
-58
FS23 °C
°F
Dec
Int
FS26 C Solar panels maximum water set
Establishes the maximum limit that can be utilised to set the solar
panels setpoint
FS23 110.0
230
°C
°F
Dec
Int
FS27 C Domestic hot water outlets inversion delay from starting of
domestic hot water pump
0250Sec
FS28 C Domestic hot water pump off delay from inversion of domestic
hot water outlets
0250Sec
FS29 C Maximum holding time in Anti-Legionella function 0 250 Min
FS30 C Domestic hot water production suspension setpoint -50.0
-58
110.0
230
°C
°F
FS31 C Domestic hot water production re-enabling differential 0.1
0
25.0
45
°C
°F
FS32 C Domestic hot water production suspension minimum duration 0 250 Min
FS33 C Domestic hot water pump continuous operation enabling 0 1
FS34 C Free cooling pump off time for units with exclusively Free
cooling
0250Min
FS35 C Free cooling pump on time for units with exclusively Free cooling 0 250 Sec
FS36 C Maximum holding time in Free cooling 0 250 Min
FS37 C Free cooling control setpoint -50
-58
110.0
230
°C
°F
Dec
Int
FS38 C Free cooling control proportional band 0.1
0
25.0
45
°C
°F
Dec
Int
FS39 C Free cooling valve outlet minimum value 0 100 %
FS40 C Free cooling valve outlet maximum value 0 100 %
FS41 C Selection of T1 probe for Free cooling:
0= Disabled
1= Pb1
2= Pb2, others.
020
FS42 C Selection of T1 probe for Free cooling:
0= Disabled
1= Pb1
2= Pb2, others.
020
Parameter Level Description Min. Max. UM Resolution