Operation mode
T: Set time t1, t2, t3, ta<T
Operation type
Power on delay (1)
Explanation Time chart
• Set the operation mode
section of the DIP switches
(no.’s 1, 2, and 3) on the
side of the timer as shown.
Clears elapsed time value and starts time
delay at power ON.
• After timer completion, stops at the display of
the set value (addition), or stops at “0” (sub-
traction).
• Ignores start input.
A
Power on delay (2)
A2
Signal on delay
B
Signal off delay
C
TT
ON
OFF
ON
OFF
ON
OFF
Reset
Output
Power
supply
T T
ON
OFF
ON
OFF
ON
OFF
Reset
Output
Power
supply
T T
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Start
Reset
Output
Power
supply
T>t1 T>t2
t2t1T
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Start
Reset
Output
Power
supply
123
ON ON ON
• Set the operation mode
section of the DIP switches
(no.’s 1, 2, and 3) on the
side of the timer as shown.
Elapsed time value does not clear at power
ON. (power outage countermeasure func-
tion)
• The output remains ON even after the power
is cut and restarted.
• After timer completion, stops at the display of
the set value (addition), or stops at “0” (sub-
traction).
• Ignores start input.
123
OFF OFF OFF
• Set the operation mode
section of the DIP switches
(no.’s 1, 2, and 3) on the
side of the timer as shown.
• Clears elapsed time value at power ON.
• Time delay starts at start ON and elapsed
time value or output resets at start OFF.
• Instantaneous time delay start at reset OFF
and power ON while start is ON.
• In order to have the time delay start at power
ON or reset at power OFF, short out the start
input beforehand.
123
ON OFF OFF
• Set the operation mode
section of the DIP switches
(no.’s 1, 2, and 3) on the
side of the timer as shown.
• Clears elapsed time value at power ON.
• Output control ON at start ON and time delay
start at start OFF.
• Elapsed time value clears when start goes ON
again during time delay.
123
OFF ON OFF
Note: Each signal input (start and reset) is applied by shorting their input terminal to the common terminal Q.