What to do if there is an alarm in the display of Nederman Fan Inverter?
- MmelanieowensNov 1, 2025
If you see an alarm in the display of your Nederman Control Systems unit, it could be due to several reasons. It might be because the PID1 supervision is equal to the low pressure level. In this case, refer to the section on 'Alarm flashlight flashing' for guidance and reset the alarm using the BACK/RESET button once corrected. Another cause could be 'AI Low', indicating a pressure sensor issue. Check if the pressure sensor is disconnected and correct the connection according to the circuit diagram. Also, verify that the pressure hose is connected to the correct port (lower or minus port). If the sensor is faulty, consider replacing it. For other alarms or faults, consult the VACON 100 HVAC Application Manual and the documentation for any unit connected to the Fan Inverter, or consult a Ne...