Motor Protector Series Operating Instruction (V1.0)
NA704LNA708LNA712L
Main Functions
Current display: display three average current, press key to display ABC phase current
respectively.
Underload protecting: when three phase average current lower then setting current, circuit
protects and load opens.
Overload protecting: when three phase average current exceed rated current, circuit protects and
load opens.
Deficient-phase protecting: when testing deficient-phase or three phase current unbalance, circuit
protects and load opens.
Auto reset: when circuit protects and load opens, can set “reset automatically” degree and time,
after some time, switch on load again, if circuit still has malfunction, try several times, then must reset
manually.
¤ Main Technique Index
Current display range: 050A (NA704L),0100A (NA708L),
0120A (NA712L),precision ±2%
Rating current range:
Sort
Min(A)
Max(A)
NA704L
1.0
40.0
NA708L
2
80
NA712L
2
120
Underload protect action time: 0.530s (adjustable)
Overload protect action time: 0.530s (adjustable)
deficient-phase protect action time: 0.530s (adjustable)
Power supply: AC 220V±10%
Operating environment: temperature -10℃~45humidity≤85%.
Relay contact capability: 2A/250VAC (pure resistive load)
Executive standard: Q/320585 XYK 03
Operating Guide
The meaning of the LED
LED
light
flash
phase A
Display the current of phase A
-
ABC LED no light means
display three phase average
current
phase B
Display the current of phase B
-
phase C
Display the current of phase C
-
Alarm
Circuit protecting, Load
opens
Circuit protects ever, but
already reset automatically
The meaning of the nixietube display
In normal, controller displays three phase average current(unit: A), press “SEL”, then display
ABC phase current respectively. In the alarm state, it displays alarm code.
Alarm codes:
Code
Explanation
OL. overflow
Current exceed measure rangeNA704L measure range 50A
NA708L measure range 100A, NA712L measure range 140A
LAC
Load current lower than setting current
OVL overload Load current exceed rated current
PHA deficient-phase
Deficient-phase or three phase current unbalance
How to display ABC phase current?
Press “SELthen display ABC phase current respectively, the correspond LED lights. If
ABC three LED is unlighted, mean that controller display three average current.
How to reset from the alarm state?
When overload or deficient-phase protection occurs, alarm LED lights, and protection circuit
activates, the load opens, finally the state of open locks. You can set “reset automatically” degree and time,
after some time, switch on load again, if circuit still has malfunction, try several times, then must reset
manually. In any time, if press “RST”, reset from the alarm state.
How to set the parameter?

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Newasia Motor Protector Series and is the answer not in the manual?

Newasia Motor Protector Series Specifications

General IconGeneral
BrandNewasia
ModelMotor Protector Series
CategoryProtection Device
LanguageEnglish