Motor Protector Series Operating Instruction (V1.0)
NA704LNA708LNA712L
Main Functions
Current display: display three average current, press key to display ABC phase current
respectively.
Underload protecting: when three phase average current lower then setting current, circuit
protects and load opens.
Overload protecting: when three phase average current exceed rated current, circuit protects and
load opens.
Deficient-phase protecting: when testing deficient-phase or three phase current unbalance, circuit
protects and load opens.
Auto reset: when circuit protects and load opens, can set “reset automatically” degree and time,
after some time, switch on load again, if circuit still has malfunction, try several times, then must reset
manually.
¤ Main Technique Index
Current display range: 050A (NA704L),0100A (NA708L),
0120A (NA712L),precision ±2%
Rating current range:
Sort
Min(A)
Max(A)
NA704L
1.0
40.0
NA708L
2
80
NA712L
2
120
Underload protect action time: 0.530s (adjustable)
Overload protect action time: 0.530s (adjustable)
deficient-phase protect action time: 0.530s (adjustable)
Power supply: AC 220V±10%
Operating environment: temperature -10℃~45humidity≤85%.
Relay contact capability: 2A/250VAC (pure resistive load)
Executive standard: Q/320585 XYK 03
Operating Guide
The meaning of the LED
LED
light
flash
phase A
Display the current of phase A
-
ABC LED no light means
display three phase average
current
phase B
Display the current of phase B
-
phase C
Display the current of phase C
-
Alarm
Circuit protecting, Load
opens
Circuit protects ever, but
already reset automatically
The meaning of the nixietube display
In normal, controller displays three phase average current(unit: A), press “SEL”, then display
ABC phase current respectively. In the alarm state, it displays alarm code.
Alarm codes:
Code
Explanation
OL. overflow
Current exceed measure rangeNA704L measure range 50A
NA708L measure range 100A, NA712L measure range 140A
LAC
Load current lower than setting current
OVL overload Load current exceed rated current
PHA deficient-phase
Deficient-phase or three phase current unbalance
How to display ABC phase current?
Press “SELthen display ABC phase current respectively, the correspond LED lights. If
ABC three LED is unlighted, mean that controller display three average current.
How to reset from the alarm state?
When overload or deficient-phase protection occurs, alarm LED lights, and protection circuit
activates, the load opens, finally the state of open locks. You can set “reset automatically” degree and time,
after some time, switch on load again, if circuit still has malfunction, try several times, then must reset
manually. In any time, if press “RST”, reset from the alarm state.
How to set the parameter?
Question and Answer IconNeed help?

Do you have a question about the Newasia Motor Protector Series and is the answer not in the manual?

Summary

Main Functions

Current Display

Displays three average current, then A, B, C phase current respectively.

Underload Protecting

Protects when average current is lower than setting current and action time.

Overload Protecting

Protects when average current exceeds rated current and action time.

Deficient-Phase Protecting

Protects on deficient-phase or three phase current unbalance.

Auto Reset

Allows automatic reset after protection, with configurable degree and time.

Main Technique Index

Operating Guide

LED Meaning

Explains the status indication of LEDs for phase A, B, C, and Alarm.

Nixietube Display Meaning

Details nixietube display for normal current and alarm codes.

How to Display Phase Current

Instructions on how to view individual phase currents using the SEL button.

How to Reset from Alarm State

Steps for manual or automatic reset from an alarm condition.

How to Set Parameter

Guide on how to access and modify device parameters.

Basic Operating Principle

Current Testing

Describes testing load current using mutual inductors through three holes.

Underload Protection

Explains protection when current is below setting and action time.

Overload Protection

Explains protection when current exceeds rated and action time.

Deficient-Phase Protection

Details protection for phase imbalance or current unbalance.

Reset Automatically

Configuration for automatic reset degree and time after protection.

Wiring Diagram

Notice

Newasia Motor Protector Series Specifications

General IconGeneral
Frequency50/60Hz
Rated Voltage380V AC
Overvoltage ProtectionAdjustable
Undervoltage ProtectionAdjustable
Phase Loss ProtectionYes
Phase Sequence ProtectionYes
Overcurrent ProtectionAdjustable
Unbalance ProtectionAdjustable