Nexus A1557 - 5.14 Alert Trip Level; 5.15 Fire Trip Level; 5.16 Panel Delay

Default Icon
30 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Document Ref: Nex8inst.doc/Rev0 09.07.00 Page 17 of 30 Originator MC Checked by AC__
This gives the option of adjusting the alert trip level of individual devices to suit particular
installation conditions. To adjust the trip level follow the procedure below:
At Step 4 within the Engineer’s Menu (see Section 5.3 above), select 0:EXTENDED MENU.
S E L E C T L E V E L 2 O P T I O N
1 : A L E R T T R I P L E V E L S
2 : F I R E T R I P L E V E L S
* N E X T P A G E # Q U I T
Select
1: ALERT TRIP LEVELS & follow on-screen instructions, selecting loop & device no.
By repeatedly pressing the button designated TOGGLE, the engineer may view the various pre-
alarm levels available.
The required level may be selected by pressing
*
OK, then
#
to quit.
5.15 Fire Trip Level
This gives the option of adjusting the fire trip level of individual devices to suit particular
installation conditions. To adjust the trip level follow the procedure below:
At Step 4 within the Engineer’s Menu (see Section 5.3 above), select 0:EXTENDED MENU.
Select 2: FIRE TRIP LEVELS.
By repeatedly pressing the button designated TOGGLE, the engineer may view the various fire
trip levels available.
The required level may be selected by pressing
*
OK, then
#
to quit.
5.16 Panel Delay
This gives the option to have a delayed response of panel and loop alarms & auxiliary relays to
a fire condition. This facility is programmed to be active during a specified period of the
day/night. The engineer must firstly set the time on/off period; this is the time of day/night
during which - if an alarm event were to occur - a delay would be effective. Secondly he must
select the period of the delay (1 - 10 minutes). Thirdly he must enable the delay for it to be
effective.