Document Ref: Nex8inst.doc/Rev0 09.07.00 Page 28 of 30 Originator MC Checked by AC__
Device type Type
Code
Condition Panel response Analogue Value Status bits
(210)
Output bits Default cause
and effect
Comments
Series 90 zone
monitor
4 Quiescent
Fire
Circuit fault
None
Fire
Remote fault
AV = 16
AV = 64
AV = 4
Echo
output bits
0 = reset
1 = test
2 = LED
Bit 0 set on
reset or clear
faults
Program LED
bit in cause
effect if required
Series 90 control
unit monitor
4 Quiescent
Alarm
Circuit fault
None
Fire
Remote fault
AV = 16
AV = 64
AV = 4
Echo
output bits
0 = fault test
1 = alarm test
2 = remote LED
Bit 0 set on
reset or clear
faults
Program LED
bit in cause
effect if required
XP95 Mini-
switch monitor
4 Quiescent
Alarm
Alert
Circuit fault
None
Fire
Alert
Remote fault
AV = 16
AV = 64
AV = 45 - 51
AV = 4
Echo
output bits
0 = fault test
1 = alarm test
2 = LED
Bit 0 set on
reset or clear
faults
Program LED
bit in cause
effect if required
XP95 Switch
monitor
4 Quiescent
Alarm
Alert
Circuit fault
None
Fire
Alert
Remote fault
AV = 16
AV = 64
AV = 45 - 51
AV = 4
Echo
output bits
0 = not used
1 = alarm test
2 = LED
Bit 0 set on
reset or clear
faults
Program LED
bit in cause
effect if required
XP95 Switch
monitor plus
4 Quiescent
Alarm
Alert
Circuit fault
None
Fire
Alert
Remote fault
AV = 16
AV = 64
AV = 45 - 51
AV = 4
Echo
output bits
0 = opto-reset
1 = alarm test
2 = LED
Bit 0 set on
reset or clear
faults
Program LED
bit in cause
effect if required
XP95 Zone
Monitor
4 Quiescent
Alarm
Circuit fault
None
Fire
Remote fault
AV = 16
AV = 64
AV = 4
Echo
output bits
0 = reset
1 = alarm test
2 = LED
Bit 0 set on
reset or clear
faults
Program LED
bit in cause
effect if required
XP95 control unit
monitor
4 Quiescent
Alarm
Circuit fault
None
Fire
Remote fault
AV = 16
AV = 64
AV = 4
Echo
output bits
0 = reset
1 = alarm test
2 = LED
Bit 0 set on
reset or clear
faults
Program LED
bit in cause
effect if required
XP95 Radio
Interface
4 Quiescent
Alarm
Circuit fault
None
Fire
Remote fault
AV = 16
AV = 64
AV = 4
Echo
output bits
0 = reset
1 = alarm test
2 = LED
Bit 0 set on
reset or clear
faults