Document Ref: Nex8inst.doc/Rev0 09.07.00 Page 29 of 30 Originator MC Checked by AC__
Device type Type
Code
Condition Panel response Analogue Value Status bits
(210)
Output bits Default cause
and effect
Comments
Series 90 optical
smoke
5 Quiescent
Fire
Alert
Fault
None
Fire
Alert
Data fault
AV = 8 to 44
AV = 55 to 127
AV = 45 to 54
AV = 0 to 7
Echo
output bits
0 = remote LED
1 = self test
2 = LED
Bit 0 and bit 2
set when device
is in fire
See note 1.
XP95 optical
smoke
5 Quiescent
Fire
Alert
Fault
None
Fire
Alert
Data fault
AV = 8 to 44
AV = 55 to 127
AV = 45 to 54
AV = 0 to 7
Echo
output bits
0 = remote LED
1 = self test
2 = LED
Bit 0 and bit 2
set when device
is in fire
See note 1.
XP95 beam
Detector
5 Quiescent
Fire
Alert
Fault
None
Fire
Alert
Data fault
AV = 8 to 44
AV = 55 to 127
AV = 45 to 54
AV = 0 to 7
Echo
output bits
0 = remote LED
1 = self test
2 = LED
Bit 0 and bit 2
set when device
is in fire
See note 1.
XP95 flame
detector
5 Quiescent
Fire
Alert
Fault
None
Fire
Alert
Data fault
AV = 8 to 44
AV = 55 to 127
AV = 45 to 54
AV = 0 to 7
Echo
output bits
0 = remote LED
1 = self test
2 = LED
Bit 0 and bit 2
set when device
is in fire
See note 1.
XP95 multi-
sensor opt/heat
detector
5 Quiescent
Fire
Alert
Fault
None
Fire
Alert
Data fault
AV = 8 to 44
AV = 55 to 127
AV = 45 to 54
AV = 0 to 7
Echo
output bits
0 = remote LED
1 = self test
2 = LED
Bit 0 and bit 2
set when device
is in fire
See note 1.
Series 90 heat
detector
6 Quiescent
Fire
Alert
Fault
None
Fire
Alert
Data fault
AV = 8 to 44
AV = 55 to 127
AV = 45 to 54
AV = 0 to 7
Echo
output bits
0 = remote LED
1 = self test
2 = LED
Bit 0 and bit 2
set when device
is in fire
See note 1.
XP95 heat
detector standard
6 Quiescent
Fire
Alert
Fault
None
Fire
Alert
Data fault
AV = 8 to 44
AV = 55 to 127
AV = 45 to 54
AV = 0 to 7
Echo
output bits
0 = remote LED
1 = self test
2 = LED
Bit 0 and bit 2
set when device
is in fire
See note 1.