Industrial gear unitsOperating and Assembly Instructions
58 B 1050 en-1819
Pos: 12 5 /Anlei tung en/G etrieb e/4. Inbetriebnahme/Interne Kühlanlage_01_(Inbetriebnahme) [B1050, B2050] @ 28\mod_1551349755431_388.docx @ 2492796 @ 2 @ 1
4.5 Internal cooling system (Option: CC)
Pos: 12 6 /Anlei tung en/G etrieb e/4. In betri ebna hme/I ntern e Kühla nlage_02_(Inbetriebnahme) [B1050] @ 31\mod_1552992188351_388.docx @ 2513499 @ @ 1
NOTICE!
Gear unit damage
The gear unit may be damaged by overheating.
The drive may only be commissioned after the cooling spiral has been connected to the cooling circuit, and
the cooling circuit has been put into operation.
Pos: 12 7 /Anlei tung en/G etrieb e/4. In betri ebna hme/I ntern e Kühla nlage_ 03_(I nbetri ebn ahme) [B1050 , B2050] @ 31\mod_1552992003255_388.docx @ 2513423 @ @ 1
The coolant must have a similar thermal capacity as water (specific thermal capacity at 20 °C
c=4.18 kJ/kgK). Industrial water without any air bubbles or sediments is recommended as a coolant.
The hardness of the water must be between 1 dH and 15 dH; the pH value must be between pH 7.4
and pH 9.5. No aggressive liquids may be added to the coolant!
The coolant pressure must not exceed 8 bar . The necessary quantity of coolant is 10 l / min. The
maximum permissible coolant temperature is defined during the planning phase and can be found in
the order data.
We also recommend fitting a pressure reducer at the coolant inlet to avoid damage due to excessive
pressure.
Pos: 128 /A nleit ung en/G etr ieb e/4. In betr ie bna hme/ Int ern e Kü hla nlag e_0 4_(I nbet ri ebn ahm e) [ B10 50] @ 31\ mod_1552992011876_388.docx @ 2513461 @ 8 @ 1
If there is a danger of frost the operator should add a suitable anti-freeze solution to the cooling water.
The temperature of the cooling fluid and the cooling fluid flow rate must be monitored and ensured by
the operator.
Information
Thermostat
With a thermostat in the cooling water inlet, the volume of cooling water can be adjusted to the actual
requirements.