Supply-Air Temperature Sensor (RTS-UVC)
Installation Instructions
Description
The Novar Controls Supply-Air Temperature Sensor (RTS-UVC; Figure 1) is a
precision electronic sensor designed for use with the Novar Controls Unit
Ventilator Controller (UVC), Electronic Thermostat Controller (ETC), Heat
Pump Controller, and Heat Pump Controller Plus. The sensor is mounted in the
supply airstream of the controlled heating and/or cooling equipment and uses a
two-wire signal cable to send its temperature signal to the module.
NOTE! The sensor is permanently calibrated at the factory. It
cannot be adjusted in the field.
Specifications
Wire Length: 6 feet (with the sensing element at the tip of the wire)
The wire length can be extended up to 100 feet if
necessary.
Wire gauge: Minimum 22-gauge wire.
Sensor tip diameter: 1/4 inch
Range: 20° to 144°F (–7° to 62°C)
Mounting the RTS-UVC
The sensor should be mounted in an area where the air streams are well mixed to
prevent a “stratified” temperature reading. The sensing tip and at least 6 inches
of the wire leading to the tip should be mounted in the supply airstream of the
controlled equipment. Tie-wraps or other suitable mounting hardware can be
used to secure the sensor.
DOC. #560051000—A 7/30/04 1
Figure 1. RTS-UVC Supply-Air Temperature Sensor
Question and Answer IconNeed help?

Do you have a question about the Novar RTS-UVC and is the answer not in the manual?

Summary

Description

Product Overview

Explains the RTS-UVC sensor's purpose, compatibility with Novar Controllers, and mounting in supply airstreams.

Specifications

Wire Length Specification

Details the standard 6-foot wire length and its extendibility up to 100 feet for sensor installation.

Wire Gauge Specification

Specifies the minimum 22-gauge wire required for connecting the sensor.

Sensor Tip Diameter

Provides the physical dimension of the sensor tip as 1/4 inch for mounting purposes.

Temperature Range

Defines the operational temperature range of the sensor from 20° to 144°F (-7° to 62°C).

Mounting the RTS-UVC

Optimal Sensor Mounting

Instructs to mount the sensor tip and wire in a well-mixed airstream, at least 6 inches from the tip.

Wiring the RTS-UVC

Sensor Wire Connections

Provides step-by-step instructions for connecting the sensor's red and black wires to specific module terminals.

Model and Part Number

Ordering Information

Lists the product model number (RTS-UVC) and its corresponding part number (736003000) for ordering.

Novar RTS-UVC Specifications

General IconGeneral
BrandNovar
ModelRTS-UVC
CategoryAccessories
LanguageEnglish