12.
Alarm is sounding
Water entered
Low voltage shutdown or
thermal shutdown has
occurred.
Shorten cables or use
heavier cables. Recharge
battery. Allow unit to cool.
Improve air circulation
around unit. Locate unit
to a cooler environment.
Reduce load if continuous
operation is required.
Water entered the unit
Disconnect the inverter
and wipe immediately
with a dry cloth, or
permanent damage can
occur with liquid ingress.
Standard “average-reading”
AC voltmeter used to
measure output voltage,
resulting in an apparent
reading 5 to 15V too low.
Inverter’s “modified sine
wave” output requires “
true RMS” voltmeter for
accurate measurements.
Measured
inverter
output is too low
Battery voltage is too low.
Battery run time
is less than
expected
Recharge battery.
AC product power
consumption is higher
than rated.
Battery is old or properly
defective.
Battery is not being properly
charged.
Use a larger battery to
make up for increased
power requirement.
Replace battery.
Some chargers are not
able to fully recharge a
battery. Make sure you
use a powerful charger.
Power dissipation in DC
cables.
Use shorter/heavier DC
cables.