Surveyor 4B
User Manual
DC power supply
12-volt power supply
The 12 volt power supply can be connected to the points marked 0 and 12 V
on the Surveyor 4B terminal block (see Figure 2, Item2).
The Surveyor 4B must be protected on the upstream side by a fuse (630mA)
with time-delay.
The cable must have a minimum cross section of 1.5 mm².
Power consumption: 5.8 W max. (detector connected).
Explosimetric detectors
Only explosimetric detectors of the "bridge" type can be connected to
the SV 4B.
Surveyor 4B and the detector are connected together by a shielded
cable with three active conductors. The shielded cable is to be
connected to the earth to EMC constraints at one end only.
Terminals C1, C2 and C3 of Surveyor 4B and the detector are to be
connected in opposite mode (Figure 3).
Figure 3 : Detector connections
Figure 2 : power supply connections
Item 1
Item 2