Appendix BSpecifications
185
Terminal Connections
I/O word “n”
CN1
I/O word “n+1”
CN2
AB
0
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
COM2
9
8
9
10
11
12
13
14
15
COM3
+
+
NC
10
NC
11
NC
NC
NC
12
NC
+
24 VDC
1
2
3
4
5
6
7
8
9
10
11
12
+
24 VDC
L
+5 to 24 VDC +5 to 24 VDC
B
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
COM0
+
10
NC
11
NC
8
9
10
11
12
13
14
15
COM1
+
NC
12
A
1
2
3
4
5
6
7
8
9
10
11
12
NC
5 to 24
VDC
5 to 24
VDC
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
Note 1. I/O word “n” is determined by the unit number setting (n = IR 100 + 10 × unit number).
2. The Unit will have 16 static output and16 static input points when pin 1 of it’s DIP switch is OFF.
3. At high temperatures, the number of inputs that can be turned ON simultaneously is limited. Refer to the
graph on page 187 for details.
4. When pin 2 of the Unit’s DIP switch is ON, input points 08 to 15 in connector 2 are high-speed inputs.
5. When wiring output circuits, be sure to use the correct polarity for the external power supplies. Wiring
with incorrect polarity may result in erroneous operation of the load.
24 VDC Input/Transistor Output Unit C200H-MD215
(Used as 128-point Dynamic Input Unit)
Max. Switching Capacity 100 mA 24 VDC, 800 mA/common, 1.6 A/Unit
Min. Switching Capacity None
Leakage Current 0.1 mA max.
Residual Voltage 0.7 V max.
ON Response Time 0.2 ms max.
OFF Response Time 0.6 ms max.
Fuses 2 (1 fuse/common; fuses are not user-replacable.)
Power for External Supply
45 mA 5 to 24 VDC10% min.
(2.8 mA × number of ON outputs)
Rated Input Voltage 24 VDC
Operating Input Voltage 20.4 to 26.4 VDC
Input Impedance
5.6 kW
Input Current 4.1 mA (at 24 VDC)
ON Voltage 14.4 VDC min.
OFF Voltage 5.0 VDC max.
No. of Circuits 2 (dynamic, 64 points/circuit)
Internal Current Consumption 180 mA 5 VDC max.
Weight 300 g max.
Dimensions 130×34.5×100.5 (H×W×D, in millimeters)
Output Specifications
(Connector 1)
Input Specifications
(Connector 2)
General Specifications