28 Programmable Controllers SYSMAC CS1G/H
■ Interrupt Input Unit
* Interrupt inputs are not supported on these Racks (i.e., used as normal I/O Unit).
■ Quick-response Input Unit
■ B7A Interface Unit
■ Safety Relay Unit
Unit type
Product
name
Specifications Mountable Racks
Words
required
Current
consumption
(A)
Model Standards
I/O
points
Input
voltage
Input
cur-
rent
Input pulse
width
External
connec-
tion
CPU Rack
C200HX/
HG/HE
Expansion
I/O Rack
CS1
Expansion
Rack
CS1 Long-
distance
Expansion
Rack
SYSMAC
BUS
Slave
Rack
CS1W-BC CS1W-BI
5 V
system
26 V
system
ON
time
OFF
time
@@
3
@@
2
@@
3
@@
2
CS1 Basic
I/O Units
Interrupt
Input Unit
16
inputs
24
VDC
7 mA
0.1
ms
max.
0.5
ms
max.
Remov-
able
terminal
block
Ye s Ye s N o
*
Ye s
*
Ye s
*
Ye s
No 1 word 0.10 --- CS1W-INT01
UC1, N, L,
CE
Unit type
Product
name
Specifications Mountable Racks
Words
required
Current
consumption
(A)
Model Standards
I/O
points
Input
voltage
Input
cur-
rent
Input pulse
width
(ON time)
External
connec-
tion
CPU Rack C200HX/
HG/HE
Expansion
I/O Rack
CS1
Expansion
Rack
CS1 Long-
distance
Expansion
Rack
SYSMAC
BUS
Slave
Rack
CS1W-BC CS1W-BI
5 V
system
26 V
system
@@
3
@@
2
@@
3
@@
2
CS1 Basic
I/O Units
Quick-
response
Input Unit
16
inputs
24
VDC
7 mA
0.1 ms
max.
Remov-
able
terminal
block
Ye s Ye s N o Ye s Ye s Ye s N o 1 w o r d 0 . 1 0 -- - CS1W-IDP01
UC1, N, L,
CE
Unit type
Product
name
Specifications
Mountable Racks
Words required
Current
consumption
(A)
Model Standards
CPU Rack C200HX/
HG/HE
Expansion
I/O Rack
CS1 Expansion
Rack
CS1 Long-
distance
Expansion
Rack
SYSMAC
BUS Slave
Rack
CS1W-BC CS1W-BI
5 V
system
26 V
system
@@3 @@2 @@3 @@2
CS1 Basic
I/O Unit
B7A Interface
Unit
32 inputs Yes Yes No Yes Yes Yes No 2 words 0.09 --- CS1W-B7A12
UC1, CE
32 outputs Yes Yes No Yes Yes Yes No 2 words 0.09 --- CS1W-B7A02
16 inputs/outputs Yes Yes No Yes Yes Yes No
1 input word
and 1 output
word
0.09 --- CS1W-B7A21
32 inputs/outputs Yes Yes No Yes Yes Yes No
2 input words
and 2 output
words
0.09 --- CS1W-B7A22
Unit type
Product
name
Specifications Mountable Racks
Words
required
Current
consumption
(A)
Model Standards
Func-
tion
Power
supply
voltage
Number
of input
words
Contact
type
(Safety
output)
Number
of
general
inputs
External
connec-
tions
CPU Rack
C200HX/
HG/HE
Expan-
sion I/O
Rack
CS1
Expansion
Rack
CS1 Long-
distance
Expansion
Rack
SYSMAC
BUS
Slave
Rack
CS1W-BC CS1W-BI
5 V
system
26 V
system
@@
3
@@
2
@@
3
@@
2
CS1Basic
I/O Units
Safety
Relay Unit
Emer-
gency
stop
Unit
24
VDC
1 word
or 2
words
(Shared
inputs)
DPST-
NO
4
inputs/
com-
mon
Remov-
able
termi-
nal
block
Ye s Ye s No Ye s Ye s Ye s No 1 w o r d 0 . 1 0 - - - CS1W-SF200 U, C, CE