42 Programmable Controllers SYSMAC CS1G/H
● H-PCF Optical Fiber Cables with Connectors (Black Composite Cables with Two-Optical Lines and Two Power Supply
Lines)
Note: Optical connectors for H-PCF Optical Cables with Connectors are adhesive polished.
• Cable Length
The following cable lengths are available: 2 m, 5 m, 15 m, and
20 m. For lengths of 21 m or more, contact your OMRON sales
representative.
• Model Numbers
• Optical Connector Assembly Tool
* There is a risk of quality problems when using cables assembled by typical
users, so we recommend purchasing cables with pre-attached connectors
or having a qualified technician assemble the cables.
● GI Optical Cables
A qualified technician must select, assemble, and install GI
Optical Fiber Cable, so always let an optical cable specialist
handle the GI cable.
Usable Optical Fiber Cables and Optical Connectors
• Optical fiber types: Graded, indexed, multi-mode, all quartz
glass, fiber (GI-type AGF cable)
• Optical fiber construction (core diameter/clad diameter):
62.5/125 µm or 50/125 µm
• Optical fiber optical characteristics of optical fiber: Refer to the
tables.
• Optical connectors: ST connectors (IEC-874-10)
• 50/125 µm AGF Cables
Lf is Fiber length in km, Ta is ambient temperature, and λ is the peak
wavelength of the test light source.
• 62.5/125 µm AGF Cables
Lf is Fiber length in km, Ta is ambient temperature, and λ is the peak
wavelength of the test light source.
Applicable Appearance Model Standards
Controller Link
SYSMAC LINK
S3200-CN@@@-20-20
---S3200-CN@@@-20-25
S3200-CN@@@-25-25
@@@
201
501
102
152
202
Length
2m
5m
10m
15m
20m
20
25
No. Connector lock
Half-lock
Full-loc
k
(1) 2 m, 5 m, 10 m, 15 m, 20 m
(e.g.)
S3200-CN
@@@
-20-25
(1) (2) (3)
(2) 21 m or longer
(e.g.)
S3200-CN-20-20
(1) (3)
Specify the
cable length
in meters
(2) Cable length
(3) Connectors (both ends)
(1) H-PCF
Optical Fiber Cable
Cable length
Product
name
Applicable Units Model Maker Standards
Optical
Fiber
Assembly
Tool *
This tool is used on site
for mounting crimp-cut
connectors and hard
plastic-clad silica optical
fiber for optical
transmission systems of
SYSMAC C-series
SYSBUS, SYSMAC
LINK, and Controller
Link.
CAK-0057
Sumitomo
Electric
Industries,
Ltd.
---
Items Minimum Typical Maximum Remarks
Numerical
Aperture (N.A)
--- 0.21 --- ---
Transmission
loss (dB)
--- ---
3.0Lf 0.5 km ≤ Lf
λ = 0.8 µm,
Ta = 25°C
3.0 Lf + 0.2 0.2 km ≤ Lf ≤ 0.5 km
3.0 Lf + 0.4 Lf ≤ 0.2 km
Connection
loss (dB)
--- --- 1.0 λ = 0.8 µm, one location
Transmission
band width
(MHz·km)
500 --- --- λ = 0.85 µm (LD)
Items Minimum Typical Maximum Remarks
Numerical
Aperture (N.A)
--- 0.28 --- ---
Transmission
loss (dB)
--- ---
3.5Lf 0.5 km ≤ Lf
λ = 0.8 µm,
Ta = 25°C
3.5Lf + 0.2 0.2 km ≤ Lf ≤ 0.5 km
3.5Lf + 0.4 Lf ≤ 0.2 km
Connection
loss (dB)
--- --- 1.0 λ = 0.8 µm, one location
Transmission
band width
(MHz·km)
200 --- --- λ = 0.85 µm (LD)