TM5-6115-585-34
NAVFAC
P
-
8-262-12
TO
-
35C2-3-455-2
TM
-
056840-34
(
4
)
Testing
Brushes
.
See
Operator
and
Organizational
Maintenance
Manual
.
(
5
)
Testing
Brush
Springs
.
Measure
brush
spring
tension
with
a
tension
meter
.
See
figure
5-7
.
Push
the
brush
and
take
a
reading
just
as
the
brush
pro
jects
a
little
from
the
brush
holder
.
On
a
new
brush
the
spring
tension
should
be
32
to
40
ounces
.
If
brush
spring
tension
is
below
20
ounces
,
replace
.
2
( 6 )
Testing
Solenoid
Switch
(
see
figure
5-2
)
.
(a )
Check
to
be
sure
plunger
moves
freely
in
coil
.
Measure
the
pull
-
in
coil
current
draw
by
using
Test
A.
Current
should
not
exceed
16
amps
.
(b )
Measure
the
hold
-
in
coil
draw
using
Test
B.
Current
should
not
exceed
6
amps
.
(
c
)
Total
hold
and
pull
current
draw
using
Test
C
is
22
amps
.
Total
current
draw
should
not
exceed
25
amps
.
Replace
a
bad
solenoid
.
f
.
Repair
.
1.
Tension
gauge
2.
Brush
spring
3.
Brush
TS
6115-585-34
/
5-7
(
1
)
Repairing
Starter
.
Repair
starter
by
replacing
defective
components
.
Repair
procedures
for
individ
ual
components
are
given
below
.
Figure
5-7
.
Testing
Brush
Spring
Tension
COMMUTATOR
SHAPE
GROOVE
IN
MICA
WITH
3
-
CORNERED
FILE
UNDERCUT
MICA
WITH
PIECE
OF
HACKSAW
BLADE
MICA
SEGMENT
SEGMENT
MICA
RIGHT
WRONG
MICA
MUST
BE
CUT
AWAY
CLEAN
BETWEEN
SEGMENTS
MICA
MUST
NOT
BE
LEFT
WITH
A
THIN
EDGE
NEXT
TO
SEGMENTS
TS
6115-585-34
/
5-8
Figure
5-8
.
Undercutting
Mica
5-6