EasyManuals Logo

Onelink 1042136 User Manual

Default Icon
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #8 background imageLoading...
Page #8 background image
8
Where Not to Install
Do NOT locate this Smoke/CO Alarm:
In garages, furnace rooms, crawl spaces and unfinished attics. Avoid extremely dusty, dirty or greasy areas.
Where combustion particles are produced. Combustion particles form when something burns. Areas
to avoid include poorly ventilated kitchens, garages, and furnace rooms. Keep units at least 20 feet (6
meters) from the sources of combustion particles (stove, furnace, water heater, space heater) if possible.
In areas where a 20 foot (6 meter) distance is not possible – in modular, mobile, or smaller homes, for
example – it is recommended the Smoke Alarm be placed as far from these fuel-burning sources as
possible. The placement recommendations are intended to keep these Alarms at a reasonable distance
from a fuel-burning source, and thus reduce “unwanted” alarms. Unwanted alarms can occur if a Smoke
Alarm is placed directly next to a fuel-burning source. Ventilate these areas as much as possible.
Within 5 feet (1.5 meters) of any cooking appliance. In air streams near kitchens. Air currents
can draw cooking smoke into the smoke sensor and cause unwanted alarms.
In extremely humid areas. This Alarm should be at least 10 feet (3 meters) from a shower, sauna,
humidifier, vaporizer, dishwasher, laundry room, utility room, or other source of high humidity.
In direct sunlight.
In turbulent air, near ceiling fans or open windows. Blowing air may prevent CO/smoke from reaching
the sensors.
In areas where temperature is colder than 40˚ F (4.4˚C) or hotter than 100˚ F (37.8˚C). These areas include
non air conditioned crawl spaces, unfinished attics, uninsulated or poorly insulated ceilings, porches,
and garages.
In insect infested areas. Insects can clog the openings to sensing chamber.
Less than 12 inches (305 mm) away from fluorescent lights. Electrical “noise” can interfere with the sensor.
In “dead air” spaces. See below for additional information.
Dead air” spaces may prevent smoke from reaching the Smoke/CO Alarm. To avoid dead air spaces, follow
installation recommendations below.
On ceilings, install Smoke/CO Alarms as close to the center of the ceiling as possible. If this is not possible,
install the Smoke/CO Alarm at least 4 inches (102 mm) from the wall or corner.
For wall mounting (if allowed by building codes), the top edge of Smoke/CO Alarms should be placed
between 4 inches (102 mm) and 12 inches (305 mm) from the wall/ceiling line, below typical“dead air”spaces.
On a peaked, gabled, or cathedral ceiling, install first Smoke/CO Alarm within 3 feet (0.9 meters) of the
peak of the ceiling, measured horizontally. Additional Smoke/CO Alarms maybe required depending on
the length, angle, etc. of the ceiling’s slope. Refer to NFPA 72 for details on requirements for sloped
or peaked ceilings.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Onelink 1042136 and is the answer not in the manual?

Onelink 1042136 Specifications

General IconGeneral
BrandOnelink
Model1042136
CategorySmoke Alarm
LanguageEnglish