Orus Programmable Thermostat User Manual
English
- 57 -
Orus Programmable Thermostat User Manual
Half the desired regulation band is set in the device.
The range for this parameter is 0.5 ÷ 5.0°C with 0.1°C resolution
The regulation period represents the duration of the regulation cycle
(activation period + deactivation period)
The value of this parameter is selectable between 10', 20' and 30'
Choose the regulation period value as follows:
10' for low thermal inertia systems
20' for medium thermal inertia systems
30' for high thermal inertia systems
Choose the regulation band value as follows:
broad band (5°C) for systems with high thermal gradient
narrow band (0.5°C) for systems with low thermal gradient
BATTERY REPLACEMENT
When the battery is almost
flat, the whole display flashes,
although it will continue to
carry out all functions.
For lower battery voltage, the
instrument will reach the flat
battery status, which causes
the display to switch off, a
reduced consumption and the
suspension of all functions
except the clock. Operation in
this status may continue until
the battery keeps a voltage
such to allow operation to the
microcontroller.