LiFePO4 1.5K/2K/3K Online UPS
Uninterruptible Power Supply System
Version: 1.0
www.orionpowersystems.com
ONLINE RT1 LITHIUM
User Manual

Questions and Answers

  • S
    Scott MarshallAug 14, 2025
    What to do if Orion Power Systems ONLINE RT1 LITHIUM Power Supply shows overload on LCD display?
    • E
      Elizabeth AliAug 14, 2025
      If your Orion Power Systems Power Supply is overloaded, it means the devices connected to it are being fed directly by the electrical network through the Bypass. To resolve this, remove some of the connected devices from the UPS output to reduce the load. If the UPS locks in Bypass mode after repeated overloads, first remove excess loads, then shut down and restart the UPS.
  • K
    kimberlywoodAug 17, 2025
    What does fault code 43 mean on Orion Power Systems ONLINE RT1 LITHIUM Power Supply?
    • M
      Mrs. Brittany ThompsonAug 17, 2025
      Fault code 43 on your Orion Power Systems Power Supply indicates that the UPS shut down automatically due to an overload at the UPS output. To fix this, remove some of the devices connected to the UPS to reduce the load, and then restart the UPS.
  • K
    Kimberly SmithAug 21, 2025
    What does fault code 49 mean on Orion Power Systems ONLINE RT1 LITHIUM Power Supply?
    • A
      Anna StoneAug 21, 2025
      Fault code 49 on your Orion Power Systems Power Supply indicates that the UPS is experiencing over input current. You should remove some of the devices connected to the UPS output to reduce the load.
  • M
    Mark McphersonAug 25, 2025
    What does fault code 14 mean on Orion Power Systems Power Supply?
    • K
      Kathleen MillerAug 25, 2025
      Fault code 14 on your Orion Power Systems Power Supply means the UPS shut down automatically because a short circuit occurred on the UPS output. You should check the output wiring and the devices connected to see if any are causing a short circuit.
  • M
    mooremarkAug 27, 2025
    Why Orion Power Systems ONLINE RT1 LITHIUM battery backup time is shorter than expected?
    • D
      Destiny JohnsonAug 27, 2025
      A shorter than expected battery backup time on your Orion Power Systems Power Supply can occur due to a few reasons: - The batteries may not be fully charged. In this case, charge the batteries for at least 5 hours and then check the capacity. - Batteries defect.
  • T
    Todd SnyderAug 30, 2025
    What does fault code 2A mean on Orion Power Systems Power Supply?
    • R
      Regina MorenoAug 30, 2025
      Fault code 2A on your Orion Power Systems Power Supply indicates that a short circuit has occurred on the charger output. Check if the battery wiring of the connected external pack is short-circuited.
  • E
    elizabeth30Sep 3, 2025
    How to fix reversed line and neutral conductors on Orion Power Systems ONLINE RT1 LITHIUM Power Supply?
    • F
      Frances MillerSep 3, 2025
      If the icons are displayed on the LCD of your Orion Power Systems Power Supply and the alarm sounds every 2 seconds, it means the line and neutral conductors of the UPS input are reversed. To correct this, rotate the mains power socket by 180° and then connect it to the UPS system.
  • R
    Randy HolmesSep 6, 2025
    Why Orion Power Systems ONLINE RT1 LITHIUM Power Supply has no indication and alarm?
    • D
      Deborah LopezSep 6, 2025
      If your Orion Power Systems Power Supply shows no indication and alarm, even though the mains is normal, it could be due to the following reasons: - The AC input power is not connected well. Check if the input power cord is firmly connected to the mains. - The AC input is connected incorrectly. Ensure you plug the AC input power cord into the correct AC input and not the UPS output.
  • C
    Cody OrtizSep 10, 2025
    How to disable EPO function on Orion Power Systems Power Supply?
    • A
      adam63Sep 10, 2025
      If the icon and warning code are flashing on the LCD display of your Orion Power Systems Power Supply, and the alarm is sounding every 2 seconds, the EPO (Emergency Power Off) function is likely activated. To disable the EPO function, set the circuit in a closed position.

Summary

Important Safety Warnings

Transportation Safety

Safety guidelines for transporting the UPS unit.

Preparation and Installation Safety

Pre-installation checks and safe installation practices.

Operational and Maintenance Safety

Safety procedures for operating and maintaining the UPS.

Battery Handling and Compliance Safety

Safety for battery replacement and FCC/EMC compliance.

Installation and Setup Procedures

Rear Panel and Operating Principle

Identification of rear panel ports and explanation of UPS operation.

UPS Installation and Mounting

Steps for installing the UPS, including rack and tower mounting.

UPS Setup and Connections

Connecting power, communication, and network interfaces.

Battery Replacement and Software Setup

Replacing batteries and installing monitoring software.

Operations and System Settings

Button and LCD Panel Controls

Understanding UPS buttons, LCD display, and indicators.

Alarm, Faults, and Wordings Index

Summary of audible alarms, fault codes, and LCD abbreviations.

UPS Configuration Parameters

Detailed settings for output voltage, frequency, ECO, and bypass modes.

Outlet and Autonomy Settings

Configuration for programmable outlets and backup time limits.

Charger, EPO, and Display Settings

Settings for charger current, EPO logic, site fault detection, and display.

Operating Mode Descriptions

Explains different UPS operating modes and their LCD displays.

Troubleshooting and Maintenance

UPS Problem Resolution

Guides users through common UPS issues and solutions.

Storage and Battery Maintenance

Procedures for storing the UPS and battery maintenance schedule.

Specifications and Support

Technical Specifications and Ratings

Detailed technical specifications and output power ratings for UPS models.

Service and Product Registration

Contact information for technical support and product registration.

Overview

The Orion Power Systems ONLINE RT1 LITHIUM is an Uninterruptible Power Supply (UPS) system designed to provide reliable power backup and protection for critical loads. This series includes LiFePO4 1.5K/2K/3K Online UPS models, offering a range of capacities to suit various needs.

Function Description:

The UPS operates as an online double-conversion system, meaning it continuously converts incoming AC power to DC to charge batteries and then converts it back to clean, stable AC power for connected devices. This ensures that the output power is isolated from utility power fluctuations, providing pure sinewave output. It features programmable outlets for non-critical loads and general outlets for mission-critical loads, allowing users to prioritize backup time during power failures. The system also includes surge protection for network/fax/phone lines and communication ports (USB, RS-232, SNMP intelligent slot) for monitoring and management. An Emergency Power Off (EPO) function is available for immediate shutdown in critical situations. The UPS supports various operating modes, including Online mode for continuous protection, ECO mode for energy saving, Frequency Converter mode for stable output frequency, and Battery mode for backup during power outages.

Important Technical Specifications:

The ONLINE RT1 LITHIUM series offers capacities of 1500VA/1350W (DC1500RT1L), 2000VA/1800W (DC2000RT1L), and 3000VA/2700W (DC3000RT1L).

  • Input:
    • Voltage Range: 160-300VAC (depending on load percentage and model), with specific low and high line transfer/comeback points. For 100-125VAC models, the input voltage range is 80-150VAC.
    • Frequency Range: 40Hz ~ 70Hz.
    • Phase: Single phase with ground.
    • Power Factor: ≥ 0.99 @ full load.
    • THDI: ≤ 5% @ 160-265VAC or 80-140VAC.
  • Output:
    • Voltage: 200/208/220/230/240VAC or 100/110/115/120/125/127VAC (adjustable).
    • AC Voltage Regulation: ± 1% (Batt. Mode).
    • Frequency Range: 47~53 Hz or 57~63 Hz (Synchronized Range); 50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz (Batt. Mode).
    • Current Crest Ratio: 3:1.
    • Harmonic Distortion: ≤ 2% THD (Linear Load); 4% THD (Non-linear Load).
    • Transfer Time: Zero (AC Mode to Batt. Mode); < 4 ms (Inverter to Bypass).
    • Waveform (Batt. Mode): Pure Sinewave.
  • Efficiency:
    • AC Mode @ full charged battery: ≥90% (1.5K), ≥91% (2K), ≥90% (3K).
    • ECO Mode @ full charged battery: ≥96%.
    • Battery Mode: ≥89% (1.5K), ≥89% (2K), ≥90% (3K).
  • Battery:
    • Type: LiFePO4 (LIFE-247500, LIFE-485000, LIFE-722500 depending on model).
    • Numbers: 1 (1.5K), 2 (2K), 3 (3K).
    • Recharge Time: 2 hours to 100% capacity @ 4A charging current.
    • Charging Current: 1/2/4(Default)/6/8A (selectable).
    • Charging Voltage: 52.5 VDC ± 1% (1.5K), 84 VDC ±1% (2K/3K).
  • Physical (RT models):
    • Dimensions (D x W x H in): 16.2 X 17.25 X 3.47 (1.5K), 20.0 X 17.25 X 3.47 (2K), 24.8 X 17.25 X 3.47 (3K).
    • Net Weight (lbs): 25.57 (1.5K), 33.5 (2K), 45.2 (3K).
  • Environment:
    • Operation Humidity: 20-95 % RH @ 0-40°C (non-condensing).
    • Noise Level: Less than 50dBA @ 1 Meter (With fan speed control).
    • IP degree: IP20.

Usage Features:

  • Installation Flexibility: Can be displayed on a desk or mounted in a 19" rack chassis. Tower stand installation is also supported.
  • User-Friendly Interface: An LCD panel provides real-time information on input/output voltage, frequency, battery status, load level, and operating mode. It also displays configuration items, warning, and fault codes.
  • Button Operation: Intuitive buttons for power on/off, alarm mute, LCD message switching, UPS self-test, setting mode entry, and bypass mode activation.
  • Configurable Settings: Users can adjust various parameters via the LCD panel, including output voltage, frequency converter mode, ECO mode, ECO voltage range, bypass enable/disable, bypass voltage/frequency range, programmable outlet settings, autonomy limitation, maximum charger current, EPO logic, and site fault detection.
  • Communication: Equipped with USB and RS-232 ports for connection to a PC, allowing for UPS shutdown/start-up scheduling and status monitoring via software. An intelligent slot supports SNMP or AS400 cards for advanced network management.
  • Network/Fax/Phone Surge Protection: Protects connected communication lines from surges.
  • Audible Alarms: Provides distinct alarm patterns for different events such as battery mode, low battery, overload, fault, and bypass mode.

Maintenance Features:

  • Battery Replacement: Batteries are user-replaceable without turning off the UPS or disconnecting the load, although caution is advised due to the presence of hazardous voltages. The manual specifies the exact battery types and quantities for each model.
  • Fault and Warning Indicators: The LCD panel displays specific fault codes and warning indicators, along with audible alarms, to help diagnose issues. A comprehensive troubleshooting guide is provided to assist users in resolving common problems.
  • Storage Guidelines: Detailed instructions for storing the UPS, including recommended temperature ranges and recharge frequencies to maintain battery health.
  • Recycling: Emphasizes the importance of delivering spent LiFePO4 batteries to a recycling facility or back to the dealer.
  • Service and Technical Support: Contact information for Orion Power Systems technical support is provided, along with instructions on what information to have ready when calling for assistance. An RMA (Returned Material Authorization) process is outlined for repairs.
  • Product Registration: Encourages users to register their product online to activate load protection guarantees and receive updates.

Orion Power Systems ONLINE RT1 LITHIUM Specifications