EasyManua.ls Logo

Osburn 2400 Insert - Page 12

Osburn 2400 Insert
34 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11
The use of an R value is convenient when more than one material is going to be used in the
hearth extension to cover the combustible surface. This is because R values are additive,
whereas K values are not. To find the corresponding R factor to use for some selected materials,
please see Table Thermal characteristics of common floor protection materials in this
section.
There are two ways to calculate the R factor of the floor protection. First, by adding the R-values
of materials used, or by the conversion if the K factor and thickness of the floor protection are
given.
To calculate the total R factor from R factors of the materials used, simply add the R-values of
materials. If the result is equal to or greater than the R-value requirements, the combination is
acceptable. To know the R-values of some selected materials, see table Thermal
characteristics of common floor protection materials.
Example:
Required floor protection R of 1.00. Proposed materials: four inches of brick and one inch
of Durock
®
board
Four inches of brick (R = 4 x 0,2 = 0,8) plus 1 inch of Durock
®
(R = 1 x 0.52 = 0.52).
0.8 + 0.52 = 1.32.
This R value is larger than the required 1.00 and is therefore acceptable
In the case of a known K and thickness of alternative materials to be used in combination,
convert all K values to R by dividing the thickness of each material by its K value. Add the R
values of your proposed materials as shown in the previous example.
Example:
K value = 0.75
Thickness = 1
R value = Thickness/K = 1/0.75 = 1.33

Related product manuals